Sec. 16-53. - Permissible sprinkler omissions.
(a) Sprinkler systems shall be designed based on complete coverage with no unprotected areas. Sprinkler coverage may be omitted from certain areas where the application of water may constitute a serious life or fire hazard. Additionally, sprinkler coverage may be omitted as provided for in NFPA 13, 13R and 13D and where approved by the fire code official. (b) Unless the use of the facility otherwise requires automatic fire sprinkler protection, automatic fire sprinklers shall not be required in the following areas: 1. Detached non-combustible Group U occupancies that do not exceed 5,000 square feet. 2. Detached non-combustible canopies that do not exceed 5,000 square feet and used for shade purposes. 3. Exterior roofs, overhangs or canopies of type I, II or III construction with no combustible storage beneath and those designed as pedestrian shade. Note: For this section, "detached" is defined as a separate single-story building or structure, without a basement or crawl space and located an approved distance from all structures. (c) In addition to automatic sprinkler systems required by this Code, other approved automatic fire protection systems may be installed to protect special hazards. These additional systems shall not substitute for the required automatic sprinkler system without approval of the fire code official.
(Ord. No. O25-52, § 2, 12-9-25)
Ask a question about Glendale law
Corpus searches the Glendale sections it holds and shows the ones that match, with their citations. Free, no sign-in.