15.56.030 - 25 decibel noise level reduction standard.

Compliance with the following standards shall be deemed to meet requirements for a minimum noise level reduction (NLR) of 25 decibels. A. General. 1. Brick veneer, masonry blocks, or stucco exterior walls shall be constructed airtight. All joints shall be grouted or caulked airtight. 2. At the penetration of exterior walls by pipes, ducts or conduits, the air space between the wall and pipes, ducts or conduits shall be caulked or filled with mortar. 3. Window and/or through-the-wall ventilation units shall not be used. 4. Through-the-wall/door mailboxes shall not be used. B. Exterior walls. 1. Exterior walls, other than described in this section, shall have a laboratory sound transmission class rating of at least STC-30. 2. Masonry walls having a surface weight of at least 25 pounds per square foot do not require a furred (stud) interior wall. At least one surface of concrete block walls shall be plastered. 3. Stud walls shall be at least four inches in nominal depth and shall be finished on the outside with siding-on-sheathing, stucco or brick veneer. a. Interior surface of the exterior walls shall be of gypsum board or plaster at least one-half inch thick, installed on the studs. b. Continuous composition board, plywood or gypsum board sheathing at least one-half inch thick shall cover the exterior side of the wall studs behind wood or metal siding. Asphaltic or wood shake shingles or plaster (stucco) are acceptable in lieu of siding. c. Sheathing panels shall be covered on the exterior with overlapping building paper. d. Insulation material at least R-11 shall be installed continuously throughout the cavity space behind the exterior sheathing and between wall studs. Insulation shall be glass fiber or mineral wool. C. Windows. 1. Windows other than as described in this section shall have a laboratory sound transmission class rating of at least STC-28. 2. Glass shall be at least 3/16 inch thick. 3. All operable windows shall be weather-stripped and airtight when closed so as to conform to an air infiltration test not to exceed 0.5 cubic foot per minute per foot of crack length in accordance with ASTM E-283-65-T. 4. Glass of fixed-sash shall be sealed in an airtight manner with a nonhardening sealant or a soft elastomer gasket or gasket tape. 5. The perimeter of window frames shall be sealed airtight to the exterior wall construction with a sealant conforming to one of the following federal specifications: TT-S-00227, TT-S-00230 or TT-S-00153. 6. Total area of glass shall not exceed 20 percent of exterior wall area. D. Doors. 1. Doors other than as described in this section shall have a laboratory sound transmission class rating of at least STC-26. 2. All exterior side-hinged doors shall be solid-core wood or insulated hollow metal at least 1¾ inches thick and shall be fully weather-stripped. 3. Exterior sliding doors shall be weather-stripped with an efficient airtight gasket system with performance as specified in subsection C3. The glass in the sliding doors shall be at least 3/16 inch thick. 4. Glass in doors shall be sealed in an airtight nonhardening sealant or in a soft elastomer gasket or glazing tape. 5. The perimeter of door frames shall be sealed airtight to the exterior wall construction as described in subsection C5. E. Roofs. 1. Combined roof and ceiling construction other than described in this section and subsection F shall have a laboratory sound transmission class rating of at least STC-39. This requires an acoustical analysis or test acceptable to the building official. 2. With an attic or rafter space at least six inches deep, and with a ceiling below, the roof shall consist of one-half inch composition board, plywood or gypsum board sheathing topped by roofing as required. 3. Open beam roof construction shall follow the energy insulation standards method for batt insulation. 4. Skylights shall conform to a STC rating of 28. F. Ceilings. 1. Gypsum board or plaster ceilings at least one-half inch thick shall be provided where required by subsection E2 above. Ceilings shall be substantially airtight with a minimum number of penetrations. 2. Glass fiber or mineral wool insulation at least R-19 shall be provided above the ceiling between joists. G. Floors. 1. Openings to any crawl spaces below the floor of the lowest occupied room shall not exceed two percent of the floor area of the occupied rooms. 2. Sleeping area floors shall be carpeted. H. Ventilation. 1. A mechanical ventilation system shall be installed that will provide the minimum air circulation and fresh air supply requirements for various uses in occupied rooms without the need to open any windows, doors, or other openings to the exterior. The attic inlet and discharge openings shall be fitted with sheet metal transfer ducts of at least 20 gauge steel, which shall be lined with one-inch thick coated glass fiber, and shall be at least five feet long with one 90-degree bend. 2. Gravity vent openings in attics shall be sized in accordance with the building code. 3. All vent ducts connecting the interior space to the outdoors, excepting kitchen and sewer gas ducts (including domestic range exhaust ducts), shall contain at least one five-foot length of internal sound-absorbing duct lining. Each duct shall be provided with a bend in the duct such that there is no direct line-of-sight through the duct from the venting cross-section to the room-opening cross-section. Duct lining shall be coated fiber duct liner at least one inch thick. 4. Fireplaces shall be fitted with well-fitted dampers.

(Ord. No. 3150, § 1, 4-15-2014; Ord. 1409, § 1 (part), 1993)

Ask a question about Henderson law

Corpus searches the Henderson sections it holds and shows the ones that match, with their citations. Free, no sign-in.