Sec. 18-245. - Fire hydrants.
(a) Required; location. Fire hydrants shall be located in buildings in underground spaces along streets and roads at not more than 500-foot (152 m) intervals, except where an automatic fire extinguishing system is provided throughout. (b) Water supply. Approved fire hydrants shall have not less than a six-inch (152 mm) connection with the water main. A valve shall be installed in the connection to the main. (c) Inlets. Each hydrant shall have a six-inch (152 mm) inlet. (d) Outlets. Each new or replacement hydrant shall have one four-inch hose outlet. (e) Pumper connection. Each hydrant shall have one four-inch pumper connection. (f) Physical protection. Each hydrant shall be protected from physical damage when subject to damage from vehicles. (g) Thrust protection. Thrust protection shall be provided at all pipe turns by installing steel anchors or thrust blocks, or by other approved methods.
(Ord. No. 200418, § 1, 6-18-20)