Sec. 9-06.34. - Standards of construction.
In all areas of special flood hazards the following standards are required:
(a) Anchoring.
(1) All new construction and substantial improvements shall be anchored to prevent flotation, collapse or lateral movement of the structure resulting from hydrodynamic and hydrostatic loads, including the effects of buoyancy.
(2) All manufactured homes shall meet the anchoring standards of Section 9-06.48.
(b) Construction Materials and Methods.
(1) All new construction and substantial improvements shall be constructed with flood-resistant materials as specified in FEMA Technical Bulletin TB 2-93 or the most recent update, and utility equipment resistant to flood damage;
(2) All new construction and substantial improvements shall be constructed using methods and practices that minimize flood damage;
(3) All new construction and substantial improvements shall be constructed with electrical, heating, ventilation, plumbing and air conditioning equipment and other service facilities that are designed and/or located so as to prevent water from entering or accumulating within the components during conditions of flooding;
(4) Require within Zones AH or AO adequate drainage paths around structures on slopes to guide flood waters around and away from proposed structures.
(c) Elevation and Floodproofing.
(1) Residential construction, new construction or substantial improvement of any structure shall have the lowest floor, including basement, elevated as follows:
(A) In an AO Zone, elevated above the highest adjacent grade to a height exceeding the depth number specified in feet on the FIRM by two feet, or elevated at least two feet above the highest adjacent grade if no depth number is specified;
(B) In an A Zone, elevated two feet (minimum) above the base flood elevation; such base flood elevation shall be determined by methods in Section 9-06.19(b) of this article.
(C) In all other zones, elevated two feet (minimum) above the base flood elevation.
Upon completion of the structure, the elevation of the lowest floor including basement shall be certified by a registered professional engineer or surveyor, and verified by the building official to be properly elevated. Such certification and verification shall be provided to the floodplain administrator both prior to pouring the foundation and immediately after such foundation pour.
(2) Nonresidential construction, new or substantial improvement, shall either be elevated to conform to Section 9-06.34(c)(1) or (2) together with attendant utility and sanitary facilities:
(A) Be floodproofed below the elevation recommended under Section 9-06.34(c)(1) so that the structure is watertight with walls substantially impermeable to the passage of water;
(B) Have structural components capable of resisting hydrostatic and hydrodynamic loads and effects of buoyancy; and
(C) Be certified by a registered professional engineer or architect that the standards of this Section 9-06.34(c)(2) are satisfied. Such certification shall be provided to the floodplain administrator.
(3) All new construction and substantial improvements with fully enclosed areas below the lowest floor (excluding basements) that are usable solely for parking of vehicles, building access or storage, and which are subject to flooding, shall be designed to automatically equalize hydrostatic flood forces on exterior walls by allowing for the entry and exit of floodwater. Designs for meeting this requirement shall follow the guidelines in FEMA Technical Bulletins TB 1-93 and TB 7-93 or most recent update, and must meet or exceed the following minimum criteria:
(A) Have a minimum of two openings having a total net area of not less than one square inch for every square foot of enclosed area subject to flooding. The bottom of all openings shall be no higher than one-foot above grade. Openings may be equipped with screens, louvers, valves or other coverings or devices provided that they permit the automatic entry and exit of floodwater; or
(B) Be certified by a registered professional engineer or architect, to comply with the local floodproofing standards approved by the Federal Insurance Administration.
(4) Manufactured homes shall also meet the standards in Section 9-06.48.
(5) All development, including man-made changes to improved or unimproved real estate for which specific provisions are not specified in these regulations or the building code, shall:
(A) Be located and constructed to minimize flood damage.
(B) Meet the limitations of Section 9-06.39 of these regulations when located in a regulated floodway.
(C) Be anchored to prevent flotation, collapse or lateral movement resulting from hydrostatic loads, including the effects of buoyancy, during conditions of the design flood.
(D) Be constructed of flood damage-resistant materials.
(E) Have mechanical, plumbing, and electrical systems above the design flood elevation or meet the requirements of ASCE 24, except that minimum electric service required to address life safety and electric code requirements is permitted below the design flood elevation provided it conforms to the provisions of the electrical part of the building code for wet locations.
(Ord. No. 2671(NCS), § 2, 9-12-2023)