Sec. 10-47. - Amendments to the adopted chapters of the International Existing Building Code(2024).
Additions to the International Existing Building Code (IEBC) are shown as underlined text. Deletions of the IEBC are shown as bracketed [strikethroughs]. Section 101.1, Title, is amended as follows: 101.1 Title. These regulations shall be known as the Existing Building Code of San Antonio, Texas, [NAME OF JURISDICTION] herein referred to as "this code." Section [A] 101.4.2, Buildings previously occupied, is amended by amending the reference to the International Property Maintenance Code to read as follows: [A] 101.4.2 Buildings previously occupied. The legal occupancy of any building existing on the date of adoption of this code shall be permitted to continue without change, except as is specifically covered in this code, the International Fire Code, or the San Antonio [International] Property Maintenance Code, or as is deemed necessary by the code official for the general safety and welfare of the occupants and the public. Section 202, GENERAL DEFINITIONS, is amended by amending the definition for Change of Occupancy to read as follows: CHANGE OF OCCUPANCY. Any of the following shall be considered as a change of occupancy where the current International Building Code requires a greater degree of safety, accessibility, structural strength, fire protection, means of egress, ventilation or sanitation than is existing in the current building or structure: 1. Any change in the occupancy classification of a building or structure. 2. A change in the purpose of, or a change in the level of activity within, a building or structure. 3. A change in use. Existing open buildings and structures that are modified such that they are no longer open on at least three sides and open a minimum of 50% of the perimeter of the area covered are also considered a change of occupancy and fire sprinklers systems shall be installed for these change in occupancies in accordance with the applicable requirements of the International Building Code and International Fire Code. In order to be considered "open" for the purpose of this requirement, an open side shall be at least 50% open with the open area uniformly distributed to prevent the accumulation of smoke and toxic gases. SECTION 306, ACCESSIBILITY FOR EXISTING BUILDINGS, is repealed in its entirety. Section 502.6, Enhanced classroom acoustics, is deleted. Section 503.18, Enhanced classroom acoustics, is deleted. Section 503.20, Two-way communications systems, is deleted. Section 506.5, Structural, is amended as follows, all other Code text remains as is: 506.5 Structural. [Any building undergoing a change of occupancy shall satisfy the requirements of this section.] The code official shall be authorized to require the compliance with this section. Section 506.6, Enhanced classroom acoustics, is deleted. Section 903.4, Enhanced classroom acoustics, is deleted. Section 1011.2.1, Automatic sprinkler system, is amended as follows: 1011.2.1 Automatic sprinkler system. The installation of an automatic sprinkler system shall be required where there is a change of occupancy classification and Chapter 9 of the current International Building Code requires an automatic sprinkler system based on the new occupancy or where there is a change of occupancy within the space where there is a different fire protection system threshold requirement in Chapter 9 of the current International Building Code than exists in the current building or space. The installation of the automatic sprinkler system shall be required within the area of the change of occupancy and areas of the building not separated horizontally and vertically from the change of occupancy by a nonrated permanent partition and horizontal assemblies, fire partition, smoke partition, smoke barrier, fire barrier or fire wall. Exceptions: 1. An automatic sprinkler system shall not be required in a one- or two-family dwelling constructed in accordance with the International Residential Code. 2. Automatic sprinkler system shall not be required in a townhouse constructed in accordance with the International Residential Code. 3. The townhouse shall be separated from adjoining units in accordance with Section R302.2 of the International Residential Code. Section 1011.4, Enhanced classroom acoustics, is deleted. Section 1101.6, Enhanced classroom acoustics, is deleted. Section 1102.2, Area limitations, is amended by adding Section 1102.2.1, Fire wall alternative, as follows: 1102.2.1 Fire wall alternative. In other than Groups H, F-1 and S-1, fire barriers and floor and roof assemblies constructed in accordance with Sections 707 and 711, respectively, of the International Building Code shall be permitted to be used in lieu of fire walls to separate the existing building from an addition for the purpose of complying with the area limitations required for the new occupancy where all of the following conditions are met: 1. The buildings (existing building and addition) are protected throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 of the International Fire Code. 2. The maximum allowable area between fire barriers, horizontal assemblies, or any combination thereof shall not exceed the maximum allowable area determined in accordance with Chapter 5 of the International Building Code without an increase allowed for an automatic sprinkler system in accordance with Section 506 of the International Building Code. 3. The fire-resistance rating of the fire barriers and horizontal assemblies shall not be less than that specified for fire walls in Table 706.4 of the International Building Code. Exception: Where horizontal assemblies are used to limit the maximum allowable area, the required fire resistance rating of the horizontal assemblies shall be permitted to be reduced by 1 hour provided the height and number of stories increases allowed for an automatic sprinkler system by Section 504 of the International Building Code are not used for the buildings.
(Ord. No. 2025-01-30-0075, § 1(Att. 1), 1-30-25)
Ask a question about San Antonio law
Corpus searches the San Antonio sections it holds and shows the ones that match, with their citations. Free, no sign-in.