§ 14.28.220 — Section 5704.2.7.4 of the 2025 California Fire Code titled "Emergency venting" is amended to read as follows
Pasadena Municipal Code, California (Supp. No. 79: codified through Ordinance No. 7469, enacted May 18, 2026) · Pasadena Municipal Code § 14.28.220
Corpus is an independent public-information project, not the official City of Pasadena website. Stable reference: corpuslaw.us/code/3c523b1c-8df7-48f6-83fc-92f3831ed9d9
14.28.220 - Section 5704.2.7.4 of the 2025 California Fire Code titled "Emergency venting" is amended to read as follows.
5704.2.7.4 Emergency venting. Stationary, above-ground tanks shall be equipped with additional venting that will relieve excessive internal pressure caused by exposure to fires. Emergency venting devices shall be listed and approved. Emergency vents for Class I, II and IIIA liquids shall not discharge inside buildings. This requirement shall also apply to each compartment of a compartmentalized tank, the interstitial space (annulus) of a secondary containment type tank, and the enclosed space of tanks of closed-top dike construction. Additionally, this requirement shall apply to spaces or enclosed volumes, such as those intended for insulation, membranes or weather shields that can contain liquid because of a leak from the primary vessel and can inhibit venting during fire exposure. The insulation, membrane or weather shield shall not interfere with emergency venting. The venting shall be installed and maintained in accordance with Section 22.7 of NFPA 30 except as modified by Section 5703.6.2.2.
(Ord. No. 7461, § 6, 11-10-2025)