SEC. 10-50903.3.9. - FLOOR CONTROL VALVES.
903.3.10 Floor control valves. Approved, supervised, indicating floor control valves and waterflow detection assemblies shall be installed at the point of connection to the riser on each floor where any of the following occur: 1. Buildings where the floor level of the highest story is located more than 30 feet above the lowest level of fire department vehicle access. 2. Buildings that are three or more stories in height. 3. Buildings that are two or more stories below the highest level of fire department vehicle access. The building fire alarm system, dedicated function fire alarm system, and/or remote annunciator panel shall be provided at an approved location, readily accessible to the fire department and shall indicate the floor of activation of all floor control valves and waterflow detection assemblies. Exception: Waterflow detection and floor control valve assemblies shall not be required [in] Group R-3 and R-3.1 occupancies.
(Added Ord. 2025-039, § 3, eff. 10-31-25).