§ 18.40.620 — Amend CBC Section 3007.6.1—Access to interior exit stairway or ramp

Long Beach Municipal Code (Supp. No. 53, Update 1: codified through Ordinance No. ORD-26-0027, enacted October 13, 2026) · Long Beach Municipal Code § 18.40.620

Corpus is an independent public-information project, not the official City of Long Beach website. Stable reference: corpuslaw.us/code/3d2b85cc-4855-4247-9538-eb6f53b137a9

18.40.620 - Amend CBC Section 3007.6.1—Access to interior exit stairway or ramp.

Section 3007.6.1 of the California Building Code is amended to read as follows: 3007.6.1 Access to interior exit stairway or ramp. The enclosed fire service access elevator lobby shall have direct access from the enclosed elevator lobby to a smokeproof enclosure with an interior exit stairway or ramp complying with Section 909.20. Exception: Access to a smokeproof enclosure with an interior exit stairway or ramp shall be permitted to be through a protected path of travel that has a level of fire protection not less than the elevator lobby enclosure. The wall and floor/ceiling assemblies of the protected path shall comply with the requirements of Section 3007.6.2 and doors opening into the protected path shall comply with the requirements of Section 3007.6.3. The protected path shall be separated from the enclosed elevator lobby through an opening protected by a smoke and draft control assembly in accordance Section 716.2.2.1.

(ORD-25-0019 § 1(Exh. A), 2025)