Sec. 49-1905. - Valves and controls.
The following provisions shall apply to sprinkler system valves and controls: (a) All single-family lawn sprinkler systems and all other systems of 50 heads or less with a one inch or smaller tap may be equipped with an approved pressure vacuum breaker (PVB). (b) All other installations shall require a reduced principle backflow preventer assembly approved by the plumbing board and the Metropolitan Utilities District. (c) All pressure vacuum breakers (PVB) must be installed outside of the building. (d) A reduced pressure backflow preventer assembly can be installed inside a building if approved drainage is provided. (e) Copper pipe shall be run from the discharge side of a backflow preventer to approximately eight inches below grade. If the backflow assembly is within three feet of the building foundation, the copper pipe shall continue perpendicular to the building at least three feet from the building. (f) An atmospheric vacuum breaker shall not be used on a pressurized main line. (g) Any sprinkler system on which a chemical or fertilizer injection system has been installed shall have a reduced pressure principle backflow preventer assembly installed according to this Code.
(Ord. No. 40524, § 1, 10-20-15)