1103.5.4.1. Additional Requirements.

The following additional requirements shall apply: 1. Valves and devices. A sprinkler control valve and a waterflow detecting device shall be provided at the lateral connection to the riser for each floor. 2. Monitoring. A supervisory signal shall be provided to indicate a condition that will impair the satisfactory operation of the sprinkler system. This shall include, but not be limited to, monitoring control valves, fire pump power supplies, and pump running conditions. Such signals shall be monitored in accordance with California Fire Code Section 903.4.1 and NFPA 72. 3. Water supply. The minimum water supply requirement for the sprinkler shall be determined without regard to inside hose stream demand. 4. Standpipe conversion. Existing standpipes may be converted to sprinkler risers, provided that they are hydrostatically tested for two hours at not less than 50 psi (345 Pa) in excess of the maximum pressure to be maintained in the system. Standpipe hose connection(s) shall be provided per NFPA 14. 5. Supports. Additional hangers, braces, restraints, or other attachments for support of existing standpipes (which have been converted) shall be provided if they are necessary to meet the requirements of NFPA 13. The installation of additional flexible fittings in such risers is not required.

Ask a question about San Francisco law

Corpus searches the San Francisco sections it holds and shows the ones that match, with their citations. Free, no sign-in.