Sec. 12-117. - Construction requirements for private water supply systems.
The following regulations, specifications and requirements shall be complied with in the construction of private water supply systems:
(1) Prior to the construction of any private water well in the city, plans and specifications shall be approved by the Douglas County health department and the city division of permits and inspections of the planning department. A permit for construction shall be obtained from the Douglas County health department only after plans and specifications have been approved by both the Douglas County health department and the city division of permits and inspections of the planning department. Plans and specifications shall be submitted on the private water supply application forms furnished by the health department.
(2) All well casings shall be constructed of durable, watertight material so as to exclude groundwater above the water-bearing stratum furnishing water to the well.
(3) When a well is cased with material which has a wall thickness greater than one-eighth inch, is of seamless or welded construction, and can be joined by watertight joints, the upper ten feet of the completed well shall be sealed with puddled clay or cement grout to a minimum of two inches in thickness in the annular space between the well casing and the drill hole. When a well is cased with material which is less than one-eighth inch in thickness, tile casing or concrete casing, the upper ten feet of the completed well shall be sealed with cement grout to a minimum of five inches in thickness in the annular space between the well casing and the drill hole.
The use of phenol-bearing bonded fiber material for well casings is prohibited.
(4) Tile-cased wells shall project a minimum of 12 inches above surrounding grade. Backfill around the casing shall be raised and tapered so that surface runoff drains away from the casing.
(5) Tile-cased wells shall be provided with a tightfitting, overlapping cover, secured in place. A gasket which contains no phenol-bearing material is recommended between the top edge of the tile and the cover.
(6) All wells constructed of tile casing shall be bailed to prevent bridging and voids in the gravel-pack.
(7) When pumps and/or storage tanks are installed on the top of the well, they shall be installed in accordance with state law.
(8) The well casing shall project at least 12 inches above the well platform or at least 12 inches above grade if no platform is required.
(9) The connection between the well casing and the pump shall be watertight and designed so that leaks in the pump will be diverted to the sloping platform. The use of splitbase pumps is prohibited.
(10) All reciprocating type pumps shall be equipped with a stuffing box or upper cylinder.
(11) Only self-priming pumps will be permitted. The use of pumps which require frequent priming is prohibited.
(12) The installation of well heads and pumping and storage equipment in a pit directly over the well is prohibited. Pits for housing storage facilities shall be located at least 30 feet from the well. No well shall be located nearer than ten feet to a structure.
(13) All plastic pipe fittings and appurtenances used in private water supply systems shall bear the seal of approval of the National Sanitation Foundation for plastic materials, pipe, fittings and appurtenances for potable water supplies.
(14) There shall be no sewer located nearer than ten feet from the well. Any sewer located between ten and 50 feet from the well shall be constructed so as to be water-tight when subjected to a hydrostatic test of ten feet of water.
(15) Discharge lines shall connect to the well at a depth of at least five feet and shall be placed at a depth of at least five feet from the well to a point inside or under the house.
(16) Wells which will no longer be used as a source of water supply shall be closed to prevent the entrance of surface water, filth or any other substance that might pollute or contaminate the groundwater. The casing may be withdrawn, if desired, and the well filled with sand to a distance of five feet above the water level. The balance of the distance to the ground surface shall be filled with clean earth, firmly tamped. If all the casing is not removed, it shall be cut away below the ground surface and the above filling procedure carried out.
(17) The drilling of test holes shall be exempted from the requirements of these regulations. Test holes shall be plugged in such a manner as to prevent the entrance of surface water or any other material that might pollute or contaminate the groundwater.
(18) The use of any well for the disposal of sewage, liquid or solid waste, rubbish, garbage or any other waste material is prohibited.
(19) No well shall be constructed which will permit the extraction of water from the ground at a depth of less than 30 feet.
(20) No well shall be left unprotected or open prior to completion.
(Code 1980, § 12-117; Ord. No. 33783, § 5(12-117), 1-9-96)