§ 511.1 — Local Standards for High-Rise Buildings and Tunnels

San Francisco Administrative Code (2026 S-96: through Ordinance 133-26, File No. 260686, approved July 23, 2026, effective August 23, 2026) · SF Fire Code § 511.1

Corpus is an independent public-information project, not the official City of San Francisco website. Stable reference: corpuslaw.us/code/4022da8c-6a36-422d-9257-a95fe10eeb9b

511.1. Local Standards for High-Rise Buildings and Tunnels.

Except as stated in the next paragraph, an approved air replenishment system shall be installed in all buildings having floors used for human occupancy located more than 120 feet (22 860 mm)1 above the lowest level of Fire Department vehicle access. This requirement shall apply for all buildings meeting this definition when the building permit application for construction was made after March 30, 2004. Exception: All buildings that are covered by this section but that are equipped with a fire service access elevator (FSAE) pursuant to California Building Code Section 3007 are not required to install an air replenishment system. The air replenishment system will provide a means for firefighters to refill air bottles for self-contained breathing apparatus (SCBA) through a permanently installed piping distribution system. The system shall be tested and maintained in accordance with San Francisco Fire Department Administrative Bulletin 5.07. The fire code official may require an air replenishment system be installed in new underground transportation or pedestrian tunnels exceeding 300 feet (91 440 mm). CODIFICATION NOTE 1. So in Ord. 39-26.

Ask a question about San Francisco law

Corpus searches the San Francisco sections it holds and shows the ones that match, with their citations. Free, no sign-in.