§ 251-11 — Automatic Fire Sprinkler Systems

Milwaukee Code of Ordinances (Volumes 1-3 revised through Common Council action of Sept. 22, 2026) · Milwaukee Code of Ordinances § 251-11

Corpus is an independent public-information project, not the official City of Milwaukee website. Stable reference: corpuslaw.us/code/43d2dca8-5fcf-4711-b64e-75b52dc4784a

251-11. Automatic Fire Sprinkler Systems.

1. WATER SUPPLY. a. General Requirements. Water supply connections, piping, and tanks shall be installed according to Milwaukee water works regulations. Recessed indicating valves shall be prohibited. Sprinkler systems containing a total of 20 or fewer sprinkler heads may be connected to domestic water piping if adequate pressure and flow are available. b. Connection to Domestic Water Supply. Where a sprinkler system connection to a domestic water supply is permitted, such connection shall be made after the water meter and ahead of the first domestic branch, unless otherwise approved by the commissioner of city development. The connection shall be equipped with an approved indicating valve, a backflow protection device, a pressure gauge and a drain valve. 2. SPRINKLER ALARMS. a. Installa-tion. The sprinkler contractor shall be responsible for the installation of an alarm bell and identification sign. b. Location. The alarm bell, identification sign and fire department connection may be located only on an exterior building wall which fronts on a street. These items shall be located in close proximity to one another, so that the alarm will indicate the location of the fire department connection to the fire department. Note: See s. 236-11-4-d-2 for the fire protection requirements for spray booths. Note: See NFPA 25 for sprinkler head replacement requirements. 3. TESTING OF AUTOMATIC FIRE SPRINKLER SYSTEMS. Automatic fire sprinkler systems shall be inspected and tested annually in accordance with NFPA 25 and NFPA 72. This does not preclude non-licensed individuals from conducting the daily, weekly, monthly, quarterly or semiannual inspection and testing activities for automatic fire sprinkler systems required under NFPA 25 and NFPA 72.

Ask a question about Milwaukee law

Corpus searches the Milwaukee sections it holds and shows the ones that match, with their citations. Free, no sign-in.