Sec. 8-173. - Service disconnect.
(a) Readily accessible location. The service disconnecting means shall be installed at a readily accessible location either immediately adjacent to or attached to the outside of a building or structure, or inside nearest the point of entrance of the service conductors. (1) Service entrance conductors shall not exceed twenty (20) feet maximum developed length unspliced between the meter housing and the main disconnect. This allows the service entrance conductors to run within the building up to twenty (20) feet and to terminate at the disconnecting means. (2) Electrical rooms containing building main disconnects located within a structure shall be located near the point of service entrance and on the exterior wall with a door leading directly outside. The door shall be identified with at least three-inch high lettering stating "Electrical Equipment Room." (3) No remote tripping device shall be allowed that will modify these requirements.
(Ord. No. 20,971, § 20, 12-16-14)