18.48.530 - CFC Chapter 9, Section 907.1—General.
Section 907.1 of Chapter 9 of the California Fire Code is amended by the addition of Sections 907.1.6 through 907.1.10 to read as follows: 907.1.6 Voluntary. Any fire alarm system not required by this code or the California Building Code shall be furnished for complete protection and meet all requirements of this code and the California Building Code, unless approved by the Fire Code Official. 907.1.7 Evacuation. Buildings over 3 stories may be required to provide building evacuation based on the floor of alarm, the floor above and the floor below, in lieu of a general alarm, at the discretion of the Fire Code Official. 907.1.8 Control panels. Fire alarm system control panels, including sprinkler monitoring panels, shall be utilized for connecting and supervising fire alarm and/or fire related equipment only. Security or similar devices shall not be connected to a fire alarm or sprinkler monitoring control panel. The use of control panels capable of this feature is subject to the following: 1. The owner of the facility where the panel is being installed shall provide an original letter, on company letterhead, to the Long Beach Fire Department stating that not now, nor in the future, will security or similar equipment be connected to the fire alarm or sprinkler monitoring control panel. 2. New and/or existing control panels installed after the adoption of this ordinance found to be in violation of this requirement shall be subject to corrective action, as determined by the Fire Code Official. 907.1.9 Remote annunciator. A remote annunciator shall be provided at the main entrance, the first suite in a multi suite building, or in a location as approved by the Fire Code Official. The remote annunciator shall have the capability to silence and reset the system via a key located in the Knox box, or other approved means. 907.1.10 Alarms. Where fire alarm systems are installed in non-sprinklered buildings an exterior horn and strobe device shall be installed and located on the address side of the building closest to the location of the remote annunciator.
(ORD-25-0019 § 1(Exh. A), 2025; ORD-22-0033 § 1(Exh. A), 2022)
Ask a question about Long Beach law
Corpus searches the Long Beach sections it holds and shows the ones that match, with their citations. Free, no sign-in.