Sec. 49-1307. - Offset vents.
In buildings having five or more branch intervals above an offset in a soil or waste stack less than 45 degrees from the horizontal shall provide a vent for both the stack above and below the offset. (a) The upper section of the offset: (1) Shall be vented as a separate stack with the connection being made at the base of the upper section of the soil or waste stack. (2) The vent stack for the upper section shall be sized for the fixture unit above the offset and may then be connected to another vent stack. (3) The size of the vent shall not be less than the diameter of the vent stack or soil and waste stack whichever is the smaller. (4) The lower section may be connected to the upper section if the vent is sized for the total load for both sections. (See Figure 49-1307(a)(4).) (b) The lower section of the offset: (1) May be vented by installing a relief vent as a vertical continuation of the soil or waste stack or by installing a yoke vent a minimum of two feet below the offset and above the next lower horizontal branch. (2) The vent shall be sized for the fixture unit load for the lower section of the soil or waste stack and carried out independently or connected to the vent stack. (See Figure 49-1307(b).)
(Ord. No. 40524, § 1, 10-20-15)