§ 26-254 — Backflow prevention assembly requirement
Code of Ordinances, City of Tupelo, Mississippi (Supp. No. 15: codified through Ordinance of March 5, 2024 and Ordinance of June 4, 2024) · Tupelo Code of Ordinances § 26-254
Corpus is an independent public-information project, not the official City of Tupelo website. Stable reference: corpuslaw.us/code/47ddffb1-e03d-4988-8a0c-6bc03a7bcafd
Sec. 26-254. - Backflow prevention assembly requirement.
(a) Elimination and protection of cross-connection. Cross-connections occurring within department's system shall be eliminated or protected with the appropriate backflow preventor. Cross-connections are eliminated by establishing an air gap between the potable and non-potable sources. Cross-connections are protected by installing the appropriate backflow preventor. It shall be the responsibility of the owner of the cross-connection to eliminate the cross-connection or protect the cross-connection with the appropriate backflow preventors. (b) Connections to sewer. Direct connections, permanent or temporary, between department's water system and a sanitary or storm sewer is prohibited. (c) Home wells. Connection to any source of water, other than the department's system, including home wells, is prohibited. (Excluding fire protection when protected by a reduced pressure principle assembly). (d) Approved backflow prevention assemblies. Only backflow prevention assemblies approved by the Mississippi State Department of Health and the City of Tupelo shall be installed. (e) Installation requirements. Reduced pressure principle assemblies and double check valve assemblies shall be installed in a manner and location that provides adequate access for testing and repair of the assembly. Reduced pressure principle assemblies and double check valve assemblies shall not be subject to possible flooding. Reduced pressure principle assemblies and double check valve assemblies shall not be installed in a pit or enclosure below ground level and shall be a minimum of twelve (12) inches above ground. For any backflow preventor on a line which is properly two (2) inches or less in diameter, PVC piping may be used to extend the line to the backflow preventor. For any backflow preventor on a line which is properly greater than two (2) inches in diameter, only rigid piping (such as ductile iron or cast iron) may be used to extend the line to the backflow preventor. (f) Potential closing plumbing system and thermal expansion. The installation of a backflow prevention device will result in a closed plumbing system within the residence or business. As such, it is the owner's responsibility to provide for thermal expansion within the closed loop system (i.e., the installation of thermal expansion devices and/or pressure relief valves). (g) Strainers. All new retrofit installations of backflow prevention devices shall include the installation of strainers located immediately upstream of the backflow device to preclude the fouling of backflow devices due to both foreseen and unforeseen circumstances occurring to the water supply system such as water main repairs, water main breaks, fires, periodic cleaning and flushing of mains. (h) Uninterruptible services. Services that require uninterrupted service will have to install two (2) backflow prevention devices in parallel to insure uninterrupted service during testing and repair of a device.
(Ord. of 11-16-99, §§ 4—4.8; Ord. of 1-3-02, §§ 4—4.8)
Ask a question about Tupelo law
Corpus searches the Tupelo sections it holds and shows the ones that match, with their citations. Free, no sign-in.