Sec. 44-173. - Wiring methods.
(a) Commercial wiring methods.
(1) Raceways required. All wiring for commercial and industrial buildings shall be installed in an approved raceway. If any part of a building or structure is commercial or industrial, the entire building or structure shall be wired as commercial or industrial regardless of the occupancy use or construction type.
Exception 1: In health care facilities, hospital grade AC or MC cable will be allowed only when traditional wiring methods will prevent compliance with 517-13 of NFPA 70.
Exception 2: Where single-family dwelling units are separated by approved two hour fire rated construction from the commercial or industrial area.
(2) Manufactured wiring systems. Notwithstanding this section, manufactured wiring systems (article 604) may be used in M occupancies as defined in the current edition of the building code adopted in chapter 43 of this Code, and shall be limited to lighting in open ceilings.
All such installations must meet the following requirements:
a. Product requirements:
1. All wiring systems must contain an insulated grounding conductor.
2. At each fixture termination, a factory installed grounding terminal must be provided for fixture grounding.
3. Conduit fill cannot exceed NFPA 70 requirements.
b. Installation requirements:
1. Hard pipe will be installed from power panel to local area where system is being used.
2. Modular wiring systems must be radially fed and maintained throughout the system.
(3) AC and MC cable. AC and MC cable containing a full size insulated grounding conductor may be installed within dwelling units, guest rooms and guest suites of Groups R-1, R-2, and I-1 occupancies. Dwelling units, guest rooms and guest suites shall be as defined in the current edition of the National Electrical Code adopted by this chapter. Groups R-1, R-2, and I-1 occupancies shall be as defined in the current edition of the building code adopted in chapter 43 of this Code.
(4) Services and feeders. All service entrance and feeder conductors shall be installed in approved raceways. All service entrance and feeder conductors for multi-family dwellings and associated buildings shall be installed in approved raceways.
Exception 1: Article 695 (Fire Pumps) shall be accepted in its entirety.
(5) Non-metallic sheathed cable(s). Non-metallic sheathed cable(s) shall not be an acceptable wiring method.
Exception 1: Where single-family dwelling units are separated by approved two hour fire rated construction from the commercial or industrial areas.
(6) Signs. All new branch circuits required by Article 600 for electric signs and outline lighting and any other circuits required for this purpose must contain an equipment grounding conductor.
(7) Request for waiver. The superintendent of permits and inspections may waive the commercial wiring restrictions in this section 44-173(a) upon written request by the electrical contractor or master electrician. A decision by the superintendent of permits and inspections to deny a waiver of the commercial wiring restrictions shall have the right to appeal to the building board of review, provided that a written application for appeal is filed within 20 days after the day the decision, notice or order was served or posted, as the case may be.
(b) Residential wiring methods.
(1) Services and feeders. All service entrance and feeder conductors installed in or on single-family and two-family dwellings shall be installed in approved raceways. All service entrance and feeder conductors for multi-family dwellings and associated buildings shall be installed in approved raceways.
(2) Branch circuits. Nonmetallic-sheathed cable (Type NM), service-entrance cable (Type SE), and underground and branch-circuit cable (Type UF) shall be permitted only in one-family, two-family, and multi-family dwellings. Type NM, Type SE, and Type UF cable can be exposed only in attics and crawl spaces.
(3) Lighting. For dwelling units, attached garages, and detached garages with electric power, at least one wall switch-controlled lighting outlet shall be installed to provide illumination on the exterior and at least one wall switch-controlled lighting outlet shall be installed to provide illumination on the interior side of outdoor entrances and exits. These switches shall be adjacent to and in the same room as the outdoor entrances and exits. A vehicle door in a garage shall not be considered as an outdoor entrance or exit.
Exception 1: Luminaires shall be permitted to be controlled by occupancy sensors that are (1) in addition to wall switches or (2) located at a customary wall switch location and equipped with a manual override that will allow the sensor to function as a wall switch.
Exception 2: At outdoor entrances, remote, central, or automatic control of luminaires shall be permitted.
(4) Kitchen countertop circuits. In all dwelling units, all kitchen countertop receptacles shall be installed per current NFPA 70 standards and must be divided equally between the circuits provided.
(5) Fan rated boxes. In all dwelling units, boxes installed in bedroom ceilings for luminaires or fans shall be fan rated. In any other areas of the dwelling where fans are to be installed, fan rated boxes shall be used.
(Code 1980, § 44-173; Ord. No. 32967, § 1(44-173), 4-20-93; Ord. No. 34505, § 1, 3-31-98; Ord. No. 34922, § 13, 6-15-99; Ord. No. 35472, § 5, 2-6-01; Ord. No. 35911, § 9, 4-2-02; Ord. No. 38207, § 3, 8-19-08; Ord. No. 38447, § 1, 6-16-09; Ord. No. 40164, § 2, 10-28-14; Ord. No. 40270, § 1, 3-3-15)