§ 8-1-10 — FIRE SPRINKLER SYSTEMS

Mesa City Code (Supp. No. 22: codified through Ordinance No. 5996, adopted March 9, 2026) · Mesa City Code § 8-1-10

Corpus is an independent public-information project, not the official City of Mesa website. Stable reference: corpuslaw.us/code/4a5e2952-7361-4515-8032-ed15dc913628

8-1-10: - FIRE SPRINKLER SYSTEMS

(A) Fire sprinkler systems must have backflow protection in accordance with Section 8-1-8 and the following. 1. DCVA: The fire sprinkler system must be connected to the domestic water distribution system only. Installation must be in compliance with Mesa standards and specifications. There must be no physical connections to auxiliary or supplementary water sources. There must be no fire suppressing chemical additives used in a customer system employing a DCVA. Drains must discharge to atmosphere by air gap. Piping materials, fittings and appurtenances must conform to National Fire Prevention Association requirements. 2. RPA: Fire sprinkler systems where any form of chemical additive is used such as antifreeze, corrosion inhibitors, and foaming agents, as well as systems connected to auxiliary water sources are health hazards and any such connections to the public water system must be protected with a reduced pressure assembly. This includes private fire lines with hydrants. 3. A water service that provides both fire and domestic water service connections to properties that have a combined water system used for domestic applications and for fire suppression must be protected using a reduced pressure assembly. Point of use protection could also be required for each connection to this line. (B) A fire sprinkler system is exempt from the provisions of this Section unless or until one of the following conditions occurs: 1. The existing detector or alarm check valve, which does not qualify as backflow protection, on the fire sprinkler system is unserviceable or requires replacement - upgrade to DCVA. 2. The fire sprinkler system is modified in any way- upgrade to DCVA. 3. The sprinkler density requirements increase - upgrade to DCVA. 4. A change in occupancy results in a more hazardous classification as determined by the City under the Fire Code - upgrade to DCVA. 5. Any form of chemical additive is used such as antifreeze, corrosion inhibitors, and foaming agents - upgrade to RPA.

(Ord. No. 5909, § 2, 12-9-24)

Ask a question about Mesa law

Corpus searches the Mesa sections it holds and shows the ones that match, with their citations. Free, no sign-in.