§ 49-1543 — Drains for backflow preventer
Omaha Municipal Code (Supp. No. 100, Update 2: codified through Ordinance No. 44760, enacted August 4, 2026) · Omaha Municipal Code § 49-1543
Corpus is an independent public-information project, not the official City of Omaha website. Stable reference: corpuslaw.us/code/4b47e07d-df05-4060-a878-050486e0f05d
Sec. 49-1543. - Drains for backflow preventer.
(a) Drains for a reduced pressure backflow preventer assembly shall be sized based on the rated flow of the assembly. See Table 49-1014 for maximum allowable flow rate for the floor drain or other approved receiving fixture. (b) Floor drains for double check valve assembly shall have a minimum two-inch drain. (c) On new construction, drains shall be located immediately adjacent to the device, but in no case more than five feet from the device. (d) For existing systems, backflow preventers shall be installed as close as possible to a floor drain with adequate surge protection.
(Ord. No. 40524, § 1, 10-20-15)