Cicero Municipal Code § 22-171 Pressure test requirements.
Sec. 22-171. - Pressure test requirements.
(a) All materials used in the construction and installation of refrigerating systems shall be suitable for the refrigerant used, and no material shall be used that will deteriorate due to the chemical action of the refrigerant or the oil or the combination of both.
(b) Every part of a refrigerating system shall be designed, constructed, and assembled to withstand safely and without injury the following required test pressures in pounds per square inch:
Refrigerant | Symbol | Test Pressure
Carbon dioxide | CO 2 | 1500
Ethane | C 2 H 6 | 1100
Propane | C 3 H 8 | 325
Ammonia | NH 3 | 300
Dichlorodifluoromethane | CCL 2 F 2 | 235
Methyl chloride | CH 3 CL | 215
Sulfur dioxide | SO 2 | 170
Isobutane | C 4 H 10 | 130
Butane | C 4 H 10 | 90
Dichlorotetrafluoroethane | C 2 CL 2 F 4 | 80
Ethyl chloride | C 2 H 5 CL | 60
Methyl formate | C 2 H 4 O 2 | 50
Dichloroethylene | C 2 H 2 CL 2 | 50
Trichloromonofluoromethane | CCL 3 F | 50
Dichloremethano | CH 2 CL 2 | 30
(c) Where the low pressure side of class A systems are protected by a safety valve, the test pressure shall be twice the pressure at which the safety valve is set.
(d) Castings used in the manufacture of compressors and other parts of refrigerating systems shall be sufficient thickness and close-grain structure to prevent porosity.
(Ord. of 7-19-1948, § 51; Code 1958, § 28-19)