Sec. 52-63. - Testing of backflow prevention devices.

(a) Tests required. Each reduced pressure principle backflow prevention assembly, double check valve assembly, and pressure vacuum breaker installed on the water system shall be tested after installation, after repairs of any kind, and annually. Any backflow preventer found to be non-functional shall be repaired and retested within 14 days of the initial test. (b) Certified testers. Only backflow preventer testers certified by the state department of health shall test backflow preventers located in the water system. (c) Notification. The water system shall notify the owner of each backflow preventer 60 days prior to the date that the backflow preventer is scheduled to be tested.

(Ord. No. 2716, § 5, 1-18-2000)