Tulsa Revised Ordinances tit. 52, ch. 2, art. 100 DEFINITIONS - Amendatory.
ARTICLE 100. - DEFINITIONS - Amendatory.
Article 100 of the National Electrical Code, 2020 Edition (NFPA 70-2020) is adopted as published, provided that the following definitions in Article 100 are added to read as follows:
Bracketing - Added. The installation of open wires, supported by metal or wood brackets, along or across the exterior of buildings.
Nationally Recognized Testing Laboratory - Added. A testing facility given this designation from the United States Occupational Safety and Health Administration (OSHA) that provides product safety testing and certification services to manufacturers.
110.12 (B) Integrity of Electrical Equipment and Connections - Amendatory. Internal parts of electrical equipment, including busbars, wiring terminals, insulators, and other surfaces, shall not be damaged or contaminated by foreign materials such as paint, plaster, cleaners, abrasives, or corrosive residues. There shall be no damaged parts that may adversely affect safe operation or mechanical strength of the equipment such as parts that are broken; bent; cut; or deteriorated by corrosion, chemical action or overheating. Damaged materials, equipment, appliances, and devices shall not be reused unless such elements have been reconditioned, tested, and placed in good and proper working condition and approved by a nationally recognized testing laboratory, or by the manufacturer of the equipment. Electrical equipment damaged by natural or man-made events shall be reused only as recommended by the manufacturer of such equipment.
210.08 (F) Outdoor Outlets. All outdoor outlets for dwellings, other than those covered in 210.8 (A) (3), Exception to (3), and for mini-split-type heating/ventilating/air-conditioning (HVAC) equipment and other HVAC units employing power conversion equipment as a means to control compressor speed, that are supplied by single-phase branch circuits rated 150 volts ot ground or less, 50 amperes or less, shall have ground-fault circuit-interrupter protection for personnel. Informational Note: Power conversion equipment is the term used to describe the components used in HVAC equipment that is commonly referred to as a variable speed drive. The use of power conversion equipment to control compressor speed differs from multistage compressor speed control. Exception: Ground-fault circuit-interrupter protection shall not be required on lighting outlets other than those covered in 210.8 (C).
210.12 Arc-Fault Circuit Interrupter Protection - Added. Arc-Fault Circuit Interrupter Protection shall be required for existing electrical systems that do not have AFCI protection when any new circuit or receptacle is added to the existing system.
210.19 (A)(4) Other Loads - Amendatory. Branch-circuit conductors that supply loads other than those specified in 210.2 and other than cooking appliances as covered in 210.19 (A)(3) shall have an ampacity sufficient for the loads served and shall not be smaller than 14 AWG. 20 ampere general-purpose branch circuits for dwellings shall supply a maximum of 10 outlets, 15 ampere general-purpose branch circuits for dwellings shall supply a maximum of 8 outlets. 20 ampere general-purpose branch circuits for other than dwellings shall supply a maximum of 8 outlets.
210.22.1 Permanent Labels - Added. Permanent labels shall be installed to indicate the address or location served by individual meters for multi-occupancy buildings. The permanent labels shall be embossed or engraved plaques, screwed or riveted to the service disconnect.
215.12.1 Color Coding; Identification of Ungrounded Conductors - Added. Where more than one nominal voltage system exists in a building, each ungrounded system conductor shall be identified by phase and system as follows:
240/120 | 208/120 | 480/277 | Phase
Black | Black | Brown | A
Orange | Red | Orange | B
Blue | Blue | Yellow | C
White | White | Natural Gray | Neutral
Other colors shall be used for special applications, such as travelers, etc.
220.0 Load Calculations - Added. Where an addition or alteration is made to an existing electrical system, an electrical load calculation shall be prepared to determine if the existing electrical service has the capacity to serve the added load, and the calculation shall be made available to the code official upon request.
230.24.1 Bracketing Prohibited - Added. There shall be no bracketing of wires to the exterior of buildings. Weather heads shall be so located that bracketing will not be necessary. This provision shall not apply to wires belonging to public utility companies providing service to existing buildings.
230.26.1 Point of Attachment for Overhead Services - Added. The point of the overhead service entrance and attachment to the electric utility company's service wires on a building shall be a minimum of ten (10) feet above the ground.
Exception: For existing structures with overhead services, the point of attachment shall be not less than nine (9) feet above the ground. Clearances shall be provided as required by the National Electrical Code.
230.28.1 Service Masts as Supports - Added. The minimum size of rigid metal conduit (RMC) shall be two (2) inches for services up to and including two hundred (200) amperes and two and one-half (2½) inches for services over two hundred (200) amperes.
250.24.1 Ungrounded Systems. Construction of new ungrounded services shall require the written special permission of the code official.
250.53 (A)(2) Supplemental Electrode Required - Added.
250.53.1 Residential Remodels and Repairs. A supplemental grounding electrode shall be required for complete residential rewires and for complete service changes. Repairs to existing services that are not replaced entirely, shall not require a supplemental grounding electrode where 25 ohms or less of resistance to earth is present.
358.12.1 Electrical Metallic Tubing (EMT) Uses Not Permitted - Added. EMT shall not be installed in concrete or underground.
422.16 (B)(5) Gas-fired central furnaces. Gas-fired furnaces supplying dwelling units shall be permitted to be connected by a flexible cord-and-plug. The cord and attachment plug shall have sufficient ampacity for the load and shall be routed or otherwise protected to prevent physical damage to the cord or attachment plug.
505.7 (A) Implementation of Zone Classification System - Amendatory. Classification of areas, engineering and design, selection of equipment and wiring methods shall be performed by a Registered Professional Engineer with expertise in Hazardous (Classified) Locations and Zone Systems. The installation of equipment and wiring methods, and inspections shall be performed by qualified persons.
506.7 (A) Implementation of Zone Classification System - Amendatory. Classification of areas, engineering and design, selection of equipment and wiring methods shall be performed by a Registered Professional Engineer with expertise in Hazardous (Classified) Locations and Zone Systems. The installation of equipment and wiring methods, and inspections shall be performed by qualified persons.
555.30 (D) Luminaires and other electrical equipment. Luminaires and electrical connections to luminaires or other electrical equipment shall be located not less than 5 feet horizontally from the nearest normal edge of the water. If a luminaire is within the 5 foot horizontal zone it must be 12 feet vertically.
682.10 Electrical Equipment and Transformers. Electrical equipment and transformers, including their enclosures, shall be specifically approved for the intended location. No portion of an enclosure for electrical equipment not identified for operation while submerged shall be located below the electrical datum plane. Luminaires or other electrical connections shall be located at least 5 feet (1524 mm) horizontally from the nearest edge of the water. If the luminaire is within 5 feet horizontally of the water edge it must be 12 foot vertically above the nearest edge of the water.
680.23 (A)(4) Voltage Limitations. No luminaries shall operate above the low voltage contact limit as defined in Section 680.2. This requirement shall apply to new installations, repair, replacement and modification of underwater luminaires. This section shall not apply to relamping if the line-voltage luminaire is protected by a Class A ground-fault circuit-interrupter.
680.23.1 Underwater Luminaire(s) (Lighting) - Added. All underwater lighting for swimming, wading, therapeutic, and decorative pools, fountains, hot tubs, and spas shall be supplied with not more than fourteen (14) volts. Where a plastic deck box is used, it shall be installed not less than two (2) feet away from the water's edge.
(Ord. No. 24936, § 1, 10-26-2022)