Sec. 40-580. - Control valves.

(a) Control valves are required on all fire services. Acceptable locations of valves in descending order of preference are: (1) Listed indicated valves at each connection into the building at least 40 feet from buildings if space permits. (2) Control valves installed in a cut-off stair tower or valve room accessible from the outside not more than ten feet from the door. (3) Valves located in risers with indicating posts arranged for outside operation. (b) Unacceptable are the key-operated valves, due to the fact that a situation could arise where the system might be shut down, and in the event of a fire the fire department may not be able to put the system back in service without the proper tool.

(Ord. No. 36424, § 1, 10-21-03)