International Fire Code—Amendments.
New Orleans City Code § 26-22
in effectSec. 26-22. - International Fire Code—Amendments.
That the following provisions of the International Fire Code, 2021 Edition, shall be deleted in their entirety and the following shall be substituted in lieu thereof:
CHAPTER 1
SCOPE AND ADMINISTRATION
SECTION 101 — SCOPE AND
GENERAL PROVISIONS
101.1 Title. These regulations shall be known and may be cited as the 2021 Fire Prevention Code of the City of New Orleans, hereinafter referred to as 'this code.'
SECTION 102 — APPLICABILITY
102.6 Historic buildings. The provisions of this code relating to the construction, alteration, repair, enlargement, restoration, relocation or moving of buildings or structures shall not be mandatory for existing buildings or structures identified and classified by the state or local jurisdiction as historic buildings when, in the opinion of the code official, such buildings or structures do not constitute a distinct hazard to life or property. Fire protection in designated historic buildings and structures shall be provided in accordance with an approved fire protection plan developed in accordance with the provisions of NFPA 909 and 914. Fire protection in designated historic buildings and structures may, at the discretion of the code official, be provided in accordance with an approved fire protection plan developed in accordance with the provisions of NFPA 909 and 914 or may be appealed to the Board of Building Standards and Appeals for equivalent fire protection.
SECTION 103 — FIRE PREVENTION
DIVISION
103.1 General. There is hereby established a fire prevention bureau to be called the Fire Prevention Division and the person in charge shall be known as the Chief of Fire Prevention. For the purpose of this code, the Chief of Fire Prevention shall be referred to as the Code Official, Fire Official, or Fire Code Official. The function of the division shall be the implementation, administration and enforcement of the provisions of this code.
103.1.1 The Department of Fire Prevention will operate pursuant to LA RS 40:1563.
103.4 Liability. The Code Official, officer, or authorized fire department employee charged with the enforcement of this code, while acting for the jurisdiction, shall not thereby be rendered liable personally, and is hereby relieved from all personal liability for any damage accruing to persons or property as a result of an act required or permitted in the discharge of official duties. No person who institutes or assists in the prosecution of a criminal proceeding under this code shall be liable to damages hereunder unless he/she acted with actual malice and without reasonable grounds for believing that the person accused or prosecuted was guilty of any unlawful act or omission.
103.5 Liability for Damages. The City of New Orleans does not assume any liability under this code for any damage to persons or property, if any, by reason of the inspection or re-inspection of buildings or structures authorized hereunder, or failure to inspect or re-inspect such buildings, or by reason of any permit issued hereunder or approval and disapproval of any equipment authorized herein.
103.5.1 The City of New Orleans hereby releases the Louisiana Fire Marshal and any other State entity from responsibility or liability for those inspections performed by the fire department, or the consequences thereof, within the City of New Orleans.
SECTION 104 — GENERAL AUTHORITY AND RESPONSIBILITIES
104.6 Official records. The Code Official shall keep official records as required by Sections 104.6.1 through 104.6.4. Such official records, except exhibition, convention, and special event plans, shall be retained for a time period not less than required by state statute.
104.6.3 Fire records. The fire department shall keep a record of fires occurring within its jurisdiction and of facts concerning the same.
104.7.2 Technical assistance. To determine the acceptability of technologies, processes, products, facilities, materials and uses attending the design, operation or use of a building or premises or equipment or activities subject to the inspection of the Fire Prevention Division, the Code Official is authorized to require the owner or agent to provide, without charge to the jurisdiction, a technical opinion and report. The opinion and report shall be prepared by a qualified engineer, specialist, laboratory, or fire safety specialty organization acceptable to the code official and shall analyze the fire safety properties of the design, operation or use of the building or premises or equipment or activities and the facilities and appurtenances situated thereon, to recommend necessary changes. The code official is authorized to require design submittals to be prepared by, and bear the stamp of, a registered design professional.
104.10 Investigations. The code official is hereby authorized and directed to enforce all the provisions of this code. For such purposes he and his designated officers and authorized fire department employees may exercise police powers as authorized by Section 40:1563.1 of the Louisiana Revised Statutes and applicable state and municipal law.
It shall be the duty of the officers of the fire prevention division to do the following:
1. Investigate the origin, cause and circumstances of fires, to determine whether arson has been committed.
2. Perform other departmental investigations as directed by the Superintendent.
3. Administer oaths and affirmations, examine witnesses, and receive evidence.
4. Issue subpoenas and subpoenas duces tecum in the same manner and with the same effect as if issued by the Council of the City of New Orleans.
5. Conduct criminal follow-up investigations in order to determine the identity of person(s) responsible for committing arson.
6. Obtain and execute warrants for those person(s) responsible for committing arson.
7. If arson has been established, arrest the arsonist(s).
104.12 Tampering with fire equipment. No person shall molest, tamper with, damage or otherwise disturb any apparatus, equipment or appurtenance belonging to or under the supervision and control of the fire department.
104.13 Tampering with barriers, etc. No person, unless authorized or a public officer acting within the scope of his public duties, shall remove, unlock, destroy, tamper with, or otherwise molest in any manner any lock, gate, door, barricade, fire scene tape, chain, enclosure, sign, tag or seal which has been lawfully installed by the fire official or by his order or under his control.
104.14 Removal of Fire Equipment. No personal shall remove, tamper with, or otherwise disturb any fire hydrant or fire appliance required to be installed or maintained under the provisions of this code except for the purpose of extinguishing fire, training purposes, recharging, or making necessary repairs, or when permitted by the fire official. Whenever a fire appliance is removed as herein permitted, it shall be replaced or reinstalled as soon as the purpose for which it was removed has been accomplished.
SECTION 105 — PERMITS
105.2.1 Refusal to issue permits. If the application for a permit describes a use that does not conform to the requirements of this code and other pertinent laws and ordinances, the fire code official shall not issue a permit.
105.2.2 Inspection authorized. Before a new operational permit is approved, the code official is authorized to inspect the receptacles, vehicles, buildings, devices, premises, storage spaces, or areas to be used to determine compliance with this code or any operational constraints required.
105.3.7 Information on the permit. The code official shall issue all permits required by this code on an approved form furnished for that purpose. The permit shall contain a general description of the operation or occupancy and its location and any other information required by the code official. Issued permits shall bear the signature of the Code Official and the person issuing said permit.
105.6 Required operational permits. The code official is authorized to issue operational permits for the operations set forth in Sections 105.6.1 through 105.6.53.
105.6.14 Exhibits and Trade Shows. An operational permit or "NOFD Reviewed Stamp" is required to operate exhibits and trade shows.
105.6.32 Open burning. An operational permit is required for the kindling or maintaining of an open fire or a fire on any public street, alley, road, or other public or private ground. Instructions and stipulations of the permit shall be strictly adhered to.
105.6.32.1 Outdoor Rubbish Fire/Land Clearing. No person shall kindle or maintain an outdoor rubbish fire without a permit. A firewatch may be required.
105.6.32.2 Open flame devices. An operational permit is required to utilize or maintain an open flame device for display, entertainment, amusement, or non-food warming purposes. Any device used to produce an open flame must be used as intended by the manufacturer of that device and shall comply with applicable safety industry standard(s). A Firewatch may be required.
105.6.38 Pyrotechnic and Flame special effects. An operational permit is required for use and handling of pyrotechnic and flame special effects materials and/or devices.
105.6.42 Airports, rooftop heliports and helistops. An operational permit is required for the operation of an airport, rooftop heliport or helistop.
105.6.44 Storage of tires, scrap tires and tire byproducts. An operational permit is required to establish, conduct or maintain storage of tires, scrap tires and tire byproducts that exceeds 2,500 cubic feet of total volume of tires, scrap tires or tire byproducts and for indoor storage of tires, scrap tires, and tire byproducts.
105.6.45 Temporary membrane structures, tents, tarps and canopies. An operational permit is required to erect air-supported temporary membrane structures, tents, tarps, or canopies having an aggregate area in excess of 150 square feet.
Exceptions:
1. Tents used exclusively for recreational camping purposes.
2. Funeral tents and curtains or extensions attached thereto, when used for funeral services.
105.6.49 Landfills (Type III Construction Demolition). An operational permit is required to operate a construction demolition landfill.
105.6.50 Institutional Facilities. An operational permit is required to operate an institutional facility as follows:
a. Daycare.
b. Group Home.
c. Residential Board & Care.
105.6.51 Annual Mobile and/or Temporary Vendors. A current operational permit is required to operate a mobile and/or temporary vendor stand.
105.6.51.1 Mardi Gras Mobile and/or Temporary Vendors. An operational permit is required to operate a Mardi Gras mobile and/or Mardi Gras temporary vendor stand.
105.6.52 Christmas Tree Retail Lots. An operational permit is required to engage in the business of retail sales of natural Christmas trees.
105.6.53 Special Event. A Special Event Permit is required through the City of New Orleans One Stop for Permits and Licenses to engage in, operate, or conduct any 'Special Event' not otherwise listed in the 'Permit Section' of this code but by the nature of such event, structures, systems, equipment, appliances, devices, materials, or activities are governed by provision of this code or in the opinion of the Code Official constitutes a fire or crowd control danger to the public.
105.7 Required construction permits. The code official is authorized to issue construction permits for work as set forth in Sections 105.7.1 through 105.7.18.
105.7.8 Flammable and combustible liquids.
4. Plans and specifications for the installation or removal of every above-ground or underground combustible or flammable liquid storage tank shall be submitted to the Fire Official for approval.
105.7.18 Temporary membrane structures, tents, tarps, and canopies. A construction permit is required to erect air-supported temporary membrane structures, tents, tarps, or canopies having an aggregate area in excess of 150 square feet.
Exceptions:
1. Tents used exclusively for recreational camping purposes.
2. Funeral tents and curtains or extensions attached thereto, when used for funeral services.
SECTION 106 — INSPECTIONS
SECTION 107 — MAINTENANCE
107.2 Confidence Testing. Equipment requiring periodic testing or operation to ensure maintenance shall be tested or operated as follows:
1. Confidence testing shall apply to all commercial establishments within the Parish of Orleans, including residential occupancies.
2. The building owner or his authorized representative shall be responsible for assuring that fire and life safety systems required by the building code or local/state fire codes are maintained in operable condition at all times. Testing of such fire and life safety systems shall be required as specified by this section, and shall be deemed reasonable proof that such systems are operable.
3. All fire and life safety systems will be tested and certified only by qualified personnel as determined by the Code Official.
4. Test results shall be recorded on forms stipulated by the New Orleans Fire Department (Copies available at New Orleans Fire Prevention Office at no cost). The completed forms shall be forwarded to the New Orleans Fire Prevention Division, 317 Decatur Street - New Orleans, LA 70130- Attention: Confidence Testing Unit. Copies shall also be maintained on the premises at all times and made available for Fire Department inspections.
5. The Fire Official shall be notified at least 48 hours before any test required by this section is performed. N.O.F.D. personnel may witness any required test and shall notify the building owner or his authorized representatives of the test they wish to witness and arrange agreeable appointments for witnessing the tests.
6. The systems to be tested and frequency of tests will be as follows:
CONFIDENCE TESTING SCHEDULE
TYPE OF SYSTEM | TEST FREQUENCY | FORM NUMBER
(1) Fire Alarm | Annually | CTF-1
(2) Stairway Door | Annually | CTF-2
(3) Fire Pump | Annually | CTF-3
(4) Standpipe/Hose Cabinet | Annually | CTF-4
(5) Automatic Sprinkler System | Annually | CTF-5
(6) Shaft Pressure | Annually | CTF-6
(7) Emergency Power | Annually | CTF-7
(8) Elevators | Annually | CTF-8
(9) Tempered Windows/Smoke Removal | Annually | CTF-9
(10) Foam Systems | Annually | CTF-10
(11) Fire Escapes Fire escapes approved as per IFC 1104.6 | Annually | CTF-11 (Testing Information) and Certifying letter from Engineer
(12) Halon/CO2 and all other gaseous systems | Annually | CTF-12 (Test Instructions) and Serviceman's Tag
(13) Range Hoods | Six (6) months | CTF-13 and Serviceman's Tag
Portable Fire Extinguishers | Annually | Louisiana Licensed Serviceman's Tag
SECTION 108 — BOARD OF BUILDING STANDARDS AND APPEALS
108.1 General. The Code Official has the authority and it is his duty, subject to the provisions of law and of this code, to pass upon a question relative to the mode, manner of construction or materials to be used in the erection or alteration of any building or other structure erected or to be erected within the City of New Orleans, which is affected by the provisions of this code, or of any existing laws applicable to the City of New Orleans and relating to the design, construction, alteration, maintenance, repair, and removal of buildings or other structures therein, and to require that such design, mode, manner of construction, or materials shall conform to the true intent and meaning of the several provisions of this code. If the Code Official rejects or refuses to issue a permit, or to approve the design, mode, manner of construction or materials proposed to be followed or used in the erection and alteration of any such building or structure, or when it is claimed that the rulings of the Code Official or the provisions of this code do not apply, or that more desirable and equally safe form of construction, from the owner's point of view, can be employed in a specific case, or whenever the owner of a building or structure shall object to any decision given by the Code Official, relative to the extent of damage sustained by any building or structure, by fire or otherwise, or to the extent or value of repairs, alterations or improvements of any existing building or replacement value thereof, the owner of the building may appeal from the decision of the Code Official to the Board of Building Standards and Appeals.
108.2 Appeals. Whenever the owner of an alleged unsafe structure or alleged public nuisance does not agree with the order from the Fire Department as to the corrections to be made, he shall have the right to appeal to the Board of Building Standards and Appeals within fifteen (15) days from the date of the order stating how he proposes to make the structure safe and, if required by the Board, shall submit detailed engineering analysis or recommendations accompanied by plans and specifications prepared by a Louisiana registered architect or a Louisiana registered civil engineer, or other substantiating data concerning the removal or other remedial steps to be taken to render the structure safe. In cases of emergency, and when the Code Official considers the structure in imminent danger of collapse, no appeal to the Board shall be permitted.
108.3 Actions. All cases in which application for appeals have been filed with the Board shall be heard, and the Board shall inform the Code Official of its decisions, stating the waivers or denials granted and conditions, if any, as they may require in each action. The decisions shall specify the variations allowed and the reason therefore, and shall be filed in the office of the Code Official within thirty (30) days of the public hearing. When building conditions are very unusual, requiring site visit, research and the like, the Code Official may grant a reasonable extension of time. Failure to file the decision shall not delay issuance of permits in accordance with a favorable vote so long as conditions attached to the permits are attached in accordance with the action of the Board. Copies of the decision shall be sent to the applicant and all parties involved in the appeal. If the order or refusal of the Code Official is affirmed, the order or refusal shall have full force and effect. If the order or refusal is modified or annulled, the Code Official shall issue an approval in accordance with the decision.
108.4 Appeals to Courts. A person, or any officer, department, commission, board, bureau, or any other agency of the City of New Orleans jointly or singularly aggrieved by a decision of the Board of Building Standards and Appeals may present to the Civil District Court of the Parish of Orleans, within thirty (30) days after filing of the decision in the office of the Board, a writ of certiorari asking for such relief and under such rules and regulations as are provided for such matters in appropriate legislation of the State of Louisiana.
SECTION 109 — VIOLATIONS
109.4 Violation penalties. Persons who shall violate a provision of this code or shall fail to comply with any of the requirements thereof or who shall erect, install, alter, repair or do work in violation of the approved construction documents or directive of the Code Official, or of a permit or certificate used under provisions of this code, shall be fined not more than $500 or imprisoned for not more than six months, or both. Each day that a violation continues after due notice has been served shall be deemed a separate offense.
109.4.2 Cease and Desist. The Code Official, in order to carry out the purposes of this code for which he is given the responsibility, supervision, licensure, or regulation, shall have the authority to order any person to cease and desist from any act or practice when it appears that such act or practice has violated, is violating, or will violate any provision of this code. When an order to cease and desist has been made via written notice of a violation, the recipient shall abate the violation. If the notice of violation is not complied with promptly, the Code Office is authorized to seek an administrative adjudication for any violation as provided in Chapter 6 of the Code of the City of New Orleans.
SECTION 110 — UNSAFE BUILDINGS
110.1.3 Imminent Danger. For any structure that is deemed by the Fire Code Official to be in imminent danger of collapse and/or constitutes a menace, the Fire Code Official shall have the authority to order the demolition of such structure for immediate abatement.
SECTION 111 — STOP WORK ORDER
111.4 Failure to comply. Any person who shall continue any work after having been served with a stop work order, except such work as that person is directed to perform to remove a violation or unsafe condition, shall be liable to a fine of not less than $300.00 or more than $500.00. Each day that a violation continues after due notice has been served shall be deemed a separate offense.
113.2 Schedule of Fees for Permits and/or Inspections. There shall be no fee for an annual Commercial Occupancy maintenance inspection and any required permit associated with that inspection, or for a follow-up inspection where any previously identified violation has been abated and no new violations are found. Any other inspection shall be subject to the following schedule of fees, which shall be the responsibility of the occupant/business owner:
SQUARE FOOTAGE FEE SCHEDULE
MORE THAN SQ. FT. | LESS THAN SQ. FT. | INSPECTION FEE
-0- 10,000 50,000 100,000 150,000 | 10,000 50,000 100,000 150,000 200,000 | 50.00 75.00 100.00 125.00 150.00
For any area in excess of 200,000 square feet, add $25.00 for each additional 50,000 square feet or any part thereof as per schedule.
FEES IN ADDITION TO INSPECTION OF PREMISES ARE AS FOLLOWS:
All permits are renewable annually unless otherwise stated
Firewatch Administrative Fee | 10% of total firewatch detail cost
Explosive Shipment Transporting (see late charges) | $50.00 per shipment
*Tents, Tarps, Canopies, or Temporary Membrane Structures (150 sq. ft. or greater) | $100.00 per event if ten or fewer total structures $500.00 per event if more than ten total structures
Blasting Operations | $75.00 per day
Bonfires | $75.00 per day
Paint Burning | $50.00 per day
**2015 Fire Prevention Code Amendments | $25.00 per packet
Cutting or Welding or Hot Work | $100.00 annually
Plan Review (Exhibit/Exposition, code compliance, fire evacuation, special event, etc.) | Per square footage fee schedule
Photo static copies of files or other records | $1.00 per page single sided
Pyrotechnic Displays (see late charges) | $100.00 per display
***Pyrotechnic Displays (Seasonal/Annual) | $500.00 per season or annually. Any modification to approved display will be deemed a new display
Class "B" Pyrotechnic License (NFPA 1123/Outdoor) | $50.00 annually
Class "C" Pyrotechnic License (NFPA 1126/Indoor) | $50.00 annually
Class "D" Flame Effect License | $25.00 annually
Class "B" and "C" Pyrotechnic License | $100.00 annually
NOFD "NO SMOKING" Signs | $5.00 each
Flammable or Combustible Liquid Storage Tank Installation or Removal | $75.00 per tank
Fumigations | Per square footage fee schedule for structures $500.00 annually for shipping containers
Fire Incident Report (Suppression Generated) | $25.00 each
Fire Investigative Report | $50.00 each
Arson Investigative Report | $100.00 each
Open Flame Device | $50.00 per month
Outdoor Rubbish Fire/Land Clearing | $75.00 per day
Special Event | Minimum $50.00 per event or as per square footage fee schedule
Annual Mobile and/or Temporary Vendor and Mardi Gras Mobile and/or Temporary Vendor. All permits expire January 31. | $50.00 per vehicle or stand
Any Permit not specifically listed above | Per square footage fee schedule
*Any structure erected for a period longer than 180 days shall comply with applicable sections of the International Building Code.
**Copies of 2015 International Fire Code books may be obtained by contacting 1-888-ICC-SAFE (422-7233).
***Seasonal/Annual Pyrotechnic Permits are issued at discretion of fire official for standard repetitive displays.
LATE FEES/CHARGES
Any operation which is commenced without a permit for which a permit is required. | Charges are tripled
Any operation which requires a firewatch, but commence without a firewatch being in place. | Administrative fees are tripled
All annual permits and licenses must be renewed within ten days of expiration date. Does not include pyrotechnic licenses. | If late, charges are doubled
Pyrotechnic/special effect permits must be applied for at least five working days prior to the display. | If late, charges are doubled
Explosive Shipment permits must be applied for at least 24 hours prior to shipment. | If late, charges are tripled
Fumigation permits must be applied for at least 24 hours prior to fumigation. | If late, charges are tripled
Exhibit/Exhibitions plans submitted or re-submitted less than 10 working days of move-in/start of event | Charges are doubled
EXCEPTIONS TO FEES AND CHARGES
a) Premises owned and operated by city, state, or federal government. Private contractors operating or providing services within these facilities are NOT EXEMPT.
b) Inspection of private residences consisting of two (2) or less units.
c) Fees for permits and/or inspections of tents, tarps, canopies, or temporary membrane structures (150 square feet or greater) shall be reduced by one half of the scheduled cost if the sponsoring person or organization is a nonprofit. For purposes of this section, the term "nonprofit" shall mean an organization that is exempt from federal income tax under Section 501(c) of the Internal Revenue Code, is a Louisiana nonprofit corporation in good standing with an Employer Identification Number issued by the Internal Revenue Service, or is a school operated by the Orleans Parish School Board or Recovery School District.
SECTION 114 — EMERGENCY RESPONSE INFORMATION PACKET
114.1 All owners/managers/operators of any high-rise structure, hospital, nursing home, industrial/manufacturing facility and any mercantile or storage establishment over 15,000 square feet gross area; or other occupancies deemed necessary by fire official shall be responsible for completion and installation of an emergency response information packet, herein after referred to as a "Firepak."
114.2 The Firepak envelope and pertinent information sheets contained within shall be provided by the Fire Prevention Division and available to the public during normal business hours at no cost.
114.3 The Firepak envelope and information sheets contained within shall be kept or stored on the ground floor in an accessible area within the fire command station, security office, and the location shall be approved by the Fire Official.
114.4 The pertinent information sheets within the Firepak shall contain the following:
1) The building address, occupancy type, square footage, height, number of elevators, location of master electrical shut-off and whether or not portions of the building can be isolated electrically, location of gas shut-off and whether or not an emergency generator has been installed. This information shall be included with a plot plan provided by the owner/manager/operator.
2) The names and telephone numbers of the building owner, manager, engineer, electrician, security chief, alarm service company and elevator service company.
3) The characteristics of building communications and the location of the security office and/or fire command station.
4) The characteristics of the sprinkler and standpipe systems, including fire pump.
5) The maximum number of employees occupying the building.
6) The number and location of employees with physical disabilities.
7) The location of supply storage.
8) The location and nature of chemical hazards.
9) The location and nature of radiological hazards.
10) The location and nature of biological hazards.
11) Whether or not any guard dogs are used for security purposes, and if so, the location of dogs and the name and telephone number of the handler.
12) Whether or not the roof supports any dead loads.
13) Whether or not there are any supporting columns in the building.
14) Type of roof supports and floor supports.
15) Whether or not the building has a basement.
16) Whether or not the building has fire doors.
17) Whether or not the building has an HVAC system, and if so, whether or not selective isolation can take place.
114.5 All owners/managers/operators shall be responsible for completion of the information sheets referred to in Section 114.4 in its entirety. Names and telephone numbers on the notification form shall be updated as changes in staff occur.
CHAPTER 2
DEFINITIONS
SECTION 202 — GENERAL DEFINITIONS
Commercial Occupancy. For the purpose of this code, all permanent building, premises, or occupiable space, other than one or two family dwellings, whose fire and life safety conditions are regulated by this code.
Department of Fire Prevention. The term Department of Fire Prevention shall be synonymous with 'fire prevention bureau', 'Fire Prevention Division' or similar term.
Exhibitor. An individual or entity engaged in the display of the products or services offered.
Exhibit. A space or portable structure used for the display of products or services.
Exposition. An event in which the display of products or services is organized to bring together the provider and user of the products or services.
Exposition Facility. A convention center, hotel, or other building at which exposition events are held.
Fire Code Official. Also known as the Chief of Fire Prevention, Code Official, Fire Official, or duly authorized representative, charged with the administration and enforcement of the Fire Prevention Code.
Fire Watch. A temporary measure intended to ensure continuous and systematic surveillance of a building or portion thereof by one or more individuals approved by the Fire Code Official for the purposes of identifying and controlling fire hazards, detecting early signs of unwanted fire, raising an alarm of fire and notifying the fire department.
Fire Watch Personnel. Uniformed fire service personnel subject to the Fire Official's orders at all times when so employed. The term 'fire watch personnel' shall be synonymous with 'firewatch,' 'standby personnel,' 'standby firefighter,' 'standby firewatch' or similar term.
Qualified Personnel. People who are regularly engaged in the business of installing, maintaining and testing specific systems as listed on the testing schedule, and are certified as such by the LA State Fire Marshal's Office or those persons approved by the Chief of Fire Prevention or his duly authorized representative. Note: Approval may require a written and/or field examination.
Test. A complete check of the system per nationally recognized standards to determine that the system functions as designed.
CHAPTER 3
GENERAL REQUIREMENTS
SECTION 301 — GENERAL
301.3 Standby Firewatch Personnel. Whenever it is essential for public safety in a place of public assembly or any other place where people congregate, due to the number of persons or the nature of the performance, exhibition, display, contest or activity, or inadequate signaling/suppression or fire protection systems, or life safety features, the Fire Official may require the employment of one or more approved firewatch personnel to be on duty at such place. Said firewatch personnel shall be subject to the Fire Official's orders at all times when so employed and shall be in uniform and remain on duty during the times such places are open to the public or while such activity is being conducted.
SECTION 307 — OPEN BURNING, RECREATIONAL FIRES AND PORTABLE OUTDOOR FIREPLACES
307.1.1 Prohibited open burning. Outdoor burning of waste material or other combustible material is prohibited unless conducted in the situations enumerated in Section 307.1.1.1 if no public nuisance is or will be created and if the burning is not prohibited by and is conducted in compliance with other applicable laws and with regulations and orders of governmental entities having jurisdiction, including air control regulations and orders. The authority to conduct outdoor burning under this code does not exempt or excuse the person responsible from the consequences of or the damages or injuries resulting from the burning. Said responsible person, or a duly authorized representative, must be present at the site of the burning while the burning is being conducted.
307.1.1.1 Outdoor burning permitted. Outdoor burning of trees, brush, grass, and other vegetation in land clearing operations may be permitted if the following conditions are met:
1. Prevailing winds at the time of the burning must be away from any habitations, the ambient air of which may be affected by smoke from the burning;
2. Care must be used to minimize the amount of dirt on the material being burned;
3. The fire shall be constantly attended by firewatch personnel until the fire is extinguished. The firewatch shall have a 2½ inch fire hose connected to an approved water supply, or other fire extinguishing equipment readily available for use. All fire extinguishing equipment shall be provided by permit applicant.
4. Heavy oil, asphaltic materials, items containing natural or synthetic rubber, or any materials other than plant growth which produce unreasonable amounts of smoke may not be burned nor may these substances be used to start a fire.
5. The burning may be conducted only between the hours of 8:00 a.m. to 1 hour before sunset. Piles of combustible material shall be of such size to allow complete reduction in the allotted time interval.
Exception: Burning conducted utilizing an approved air curtain incinerator, fire box, or similar equipment may be conducted for extended hours.
6. The burning must be controlled such that a traffic hazard is not created.
307.1.2 Training. The prohibition specified in Section 307.1.1 shall not apply to fires set for the purpose of training public firefighting personnel or building occupants, when authorized by the Fire Official.
307.2.2 Firewatch. An approved firewatch may be required.
307.4 Location. The location of the burning must be at least 1,000 feet (304.8 m) from any dwelling or structure.
Exception: Burning conducted utilizing an approved air curtain incinerator, fire box, or similar equipment may be conducted at lesser distances from dwellings or structures.
307.4.3 Portable Chimneys (Chimineas) and Outdoor Fireplaces. The outdoor burning of solid fuel (e.g., wood, charcoal) in portable chimneys and outdoor fireplaces used solely for recreational purposes is allowed, provided that the following conditions are met:
1. Fire is supervised at all times by an adult and the smoke does not become a nuisance for adjacent property owners/occupants.
2. Embers are contained within appliance by use of a spark arrester or similar device that prevents the embers from escaping.
3. Appliance is Underwriters Laboratory (U.L.) listed.
4. Appliance is used on a non-combustible surface and is a minimum of ten (10) feet away from all structures and combustible materials.
SECTION 308 — OPEN FLAMES
308.1.9 Cooking operations. Any cooking operation, conducted within structure, tent, or enclosed space (fixed or mobile), which produces smoke or grease laden vapors and is not protected by an approved exhaust hood with an approved fire extinguisher shall necessitate the employment of one or more firewatch personnel.
SECTION 310 — SMOKING
310.9 Provisions not exclusive. Any prohibition, restriction, or requirement under this section shall be in addition to any and all other prohibitions, restrictions, or requirements imposed by law, including but not limited to Chapter 66, Article II of the Code of the City of New Orleans.
SECTION 311 — VACANT PREMISES
311.2.2.1 Fire notification systems/protection in unoccupied portions of structures within the Inner Fire Limits. Each multistory structure within the Inner Fire Limits with an occupied first floor and unoccupied upper floors shall have an approved off-site monitored smoke/fire alarm system servicing the unoccupied upper floors.
SECTION 314 — INDOOR DISPLAYS
314.4.1 Firewatch required. When a vehicle is parked inside a place of assembly within a structure of mixed occupancy, such as a hotel, the requirements of Section 314.4 shall apply and additionally a standby firewatch person shall be employed as per Section 301.3. The Fire Official shall designate the number of standby firewatch personnel to be employed dependent upon the number of vehicles displayed and the configuration of such display. The standby firewatch personnel shall remain on duty for the entire duration of the vehicle display.
SECTION 319 — CONSTRUCTION DEBRIS LANDFILLS
319.1 Type III construction debris landfill. It shall be unlawful for any person, firm, or corporation to store or process any commercial, industrial, and/or construction debris or solid waste, as defined by the rules and regulations of the Louisiana Department of Environmental Quality, upon any public place, including the public sidewalks, streets, and other public places, within the corporate limits of the City of New Orleans or upon any property owned by or under the jurisdiction of the City of New Orleans, or upon any private property within the City without a permit. Any person, firm, or corporation wishing to operate a construction debris landfill, as defined by the Louisiana Department of Environmental Quality regulations for Type III facilities, must first secure a permit from the Department of Fire. Prior to issuing such a permit or permit renewal, the applicant shall furnish the Department of Fire written approval from the, Department of Safety and Permits, Department of Sanitation, Department of Public Works, and City Planning Commission certifying that the permit applicant is in compliance with the applicable rules and regulations set forth by each respective department or commission.
319.2 Storing or processing commercial debris. Any person, firm, or corporation wishing to store or process any commercial, industrial, and/or construction debris or waste on any open lot or parcel of ground within the jurisdiction of the City of New Orleans shall do so within the constraints set forth in the following requirements, subject to be verified and renewed annually:
1. A permit application shall be filed with the New Orleans Fire Prevention Division outlining the details of the proposed operation. Supplied information is to include the name, address, and telephone number of the property owner, the business owner, the agent for service, the lessee and lessor. The applicant must also submit a survey of the property that is to be utilized identifying the square number, lot number and municipal address. The survey must be performed and certified by a registered Louisiana professional land surveyor. The applicant must also submit evidence of a drainage runoff plan to assure that drainage or runoff from the property before, during, and after the filling shall not drain on adjacent property. The drainage plan must be certified by a registered Louisiana professional civil engineer. Landfill site ingress and egress shall meet the standards of the New Orleans Department of Public Works and under no circumstances shall the driveway impede the maximum flow created by any drainage ditches along the property adjacent to the property boundaries.
2. A three feet by five feet (3' × 5') sign that is plainly visible and legible from the street or roadway shall be provided for all new and existing businesses that shall display the following information:
a. Name of business;
b. Municipal address;
c. Hours of operation;
d. Fire Department permit number;
e. Louisiana Department of Environmental Quality site identification number; and
f. A description of the types of waste that can be received.
3. The landfill site may only be operated between the times of dawn to dusk, seven days a week.
4. Designated area shall be completely enclosed on all boundary lines facing a roadway with a proper, suitable, and substantial fence constructed of wood, metal, or masonry material, in sound condition, substantially free from deterioration, not less than seven feet (7') nor more than ten feet (10') high to prevent the ready entry of unauthorized persons on the premises or land to ensure proper screening of the enclosed area from public view. The fence shall be maintained in a constant state of good repair and no signage or advertising material shall be placed upon the fence.
5. An all-weather road having a minimum width of twenty feet (20') shall be provided throughout the site rendering all areas of the site readily accessible to firefighting equipment.
6. Smoking shall be prohibited within the construction debris area.
7. A telephone or radio communication equipment capable of fire department notification shall be provided by the operator/owner/applicant.
8. An operable bulldozer, front-end loader, or similar equipment shall be available on the site. A trained equipment operator shall be present during operation hours. A $50,000.00 surety bond shall be posted with the New Orleans Fire Department by the landfill operator/owner and/or property owner in order to cover the costs of:
a. Providing additional digging equipment, moving equipment, or other services related to and necessary for fighting and extinguishing a fire at the facility.
b. Conducting and completing closure activities of the facility as prescribed by local, state, and federal regulations.
c. Satisfying any outstanding fines/penalties that have been imposed by the City and reduced to a judgement or lien against the property in question.
9. A twelve inch (12") layer of soil/cover material shall be utilized to cover exposed construction debris every fifteen (15) calendar days. A log shall be kept available at the site to verify the dates that soil/cover material was utilized.
10. Burning of any materials or solid waste at the landfill facility shall be prohibited.
11. One (1) fire hydrant, supplied with a water line of no less than six inches (6") in diameter, shall be provided within eighty-five feet (85') of the front/main entry gate. Additionally:
a. Hydrants shall meet the specifications of the Sewerage and Water Board of New Orleans.
b. Hose outlet size and threads are to conform to the hose connections used by the Sewerage and Water Board of New Orleans.
c. The center of hydrant hose outlets shall not be less than eighteen inches (18") above the final grade.
12. It shall be the responsibility of every construction debris business operator or the owner of the land upon which the business is being operated to maintain the grass so that it does not exceed eighteen inches (18") in height. Additionally, the aforementioned person(s) shall maintain the area that begins outside the front fence and extends to the street's median, including the removal of any trash, debris, soil, litter, or solid waste in that area.
13. Adhere to all other provisions of City, State, and federal laws.
14. Adhere to all provisions of the Louisiana Department of Environmental Quality regulations on construction and demolition debris and wood waste landfills and processing facilities (Type III).
15. Should any of the requirements of Sections 319.1 through 319.2 not be met at any time, the departments of Safety and Permits, Fire, or Sanitation shall have the authority to cite the violator(s) and, after serving notice via United States mail services, hold a hearing before a duly authorized administrative hearing officer in accordance with Chapter 6 of the Code of the City of New Orleans. If after said hearing, a violation is determined to have occurred and be a continuing violation, the respective department may revoke any permit(s) issued, stop any and all processes and operations, and apply the $50,000.00 surety bond toward:
a. Costs of conducting and completing closure activities of the facility as prescribed by local, state, and federal regulations; or
b. Satisfaction of any outstanding fines or penalties assessed against the facility, by the City, which have been reduced to a judgment or lien against the property.
16. This ordinance shall have effect on any current owner/operator and/or property owner/operator and /or property owner operating an existing Type III Construction Demolition Landfill.
SECTION 320 — COMPOSTING
320.1 Scope. This section applies to storage and composting of agricultural waste material (hay, straw, manure, or other similar products) exceeding three thousand (3,000) cubic feet.
320.2 Permits. A permit is required from the Fire Official when storage exceeds three thousand (3,000) cubic feet. Should any of the requirements of this section not be met at any time, the Fire Official shall have the authority to cite the violator(s), and, after having given notice via United States mail service, hold a hearing before a duly authorized administrative hearing officer in accordance with Chapter 6 of the Code of the City of New Orleans. If, after the hearing, a violation is determined to have occurred and be a continuing violation, the Fire Official may revoke any permits issued, stop any and all processes and operations, and apply the $10,000.00 surety bond required by Section 320.3.
320.3 Surety bond. A $10,000.00 surety bond shall be posted with the New Orleans Fire Department by the operator/owner and/or property owner in order to cover the cost of: (1) providing additional digging equipment, moving equipment or other services related to and necessary for fighting and extinguishing a fire at the facility; (2) conducting and completing closure activities of the facility as prescribed by local, state, and federal regulations; (3) satisfying any outstanding fines or penalties which have been imposed by the City and reduced to a judgment or lien against the property in question.
320.4 General.
320.4.1 Agricultural waste material shall be stored in piles with maximum measurements of twenty (20) feet wide by fifty (50) feet long by fifteen (15) feet high.
320.4.2 Aisles between piles shall be no less than fifteen (15) feet in width.
320.4.3 Piles shall be irrigated as necessary to keep moisture levels between forty (40) to sixty (60) percent. Significant rain fall may be used to satisfy irrigation requirements.
320.4.4 Minimum ten (10) feet buffer zone is required for agricultural waste material storage set back where property lines adjoin other properties.
320.4.5 An operable front-end loader or backhoe or similar earth moving equipment shall be available on the site. A fire extinguisher with a minimum rating of 2-A:10-B:C must be on earth moving equipment at all times for use on equipment fires.
320.4.6 A trained equipment operator shall be present on site during operating hours.
320.4.7 Telephone or radio communication equipment capable of fire department notification shall be on the site during operating hours.
320.4.8 A plan for fire control and other emergencies shall be developed and routinely rehearsed by all personnel.
320.4.9 All other local, state, and federal regulations must be adhered to by owner/operator and/or property owner.
320.4.10 At closure, excess material shall be removed and the site shall be restored to usable condition.
320.4.11 Agricultural Waste Material and Composting sites must have a water supply meeting one of the following conditions:
1. Water Tank
a. minimum three thousand (3,000) gallon capacity.
b. minimum 250 gpm rated fire pump.
c. 2½ inch hose capable of reaching all parts of the site.
2. Natural Body of Water
a. minimum 250 gpm rated fire pump.
b. 2½ inch hose capable of reaching all parts of the site.
3. Hydrant (for sites less than 100,000 square feet)
a. Hydrant must be located within one hundred fifty (150) feet of site.
b. ¾ inch water supply outlet shall be provided and located such that all piles on site can be reached with seventy-five (75) feet of ¾ inch hose.
320.5 Fuel Storage. See Chapter 57 for fuel storage requirements.
CHAPTER 9
FIRE PROTECTION SYSTEMS
SECTION 901 — GENERAL
901.5 Installation acceptance testing. Before final approval and acceptance of fire suppression, alarm, detection, or any other fire protection device, including standby power facilities and fire ventilating systems in any building or structure, the installation shall be subjected to an acceptance test. The appropriate acceptance test shall be conducted by qualified personnel and deemed adequate to determine that the system or fire protection device has been properly installed and will function as intended. Acceptance test results shall be recorded on forms stipulated by the New Orleans Fire Department (forms available at the New Orleans Fire Prevention Office at no cost). The completed forms shall be forwarded to the New Orleans Fire Prevention Division, 317 Decatur Street, New Orleans, Louisiana 70130, Attention: Confidence Testing Unit. It shall be unlawful to occupy portions of a structure until the required fire protection systems that serve within that portion of the structure have been tested and approved.
901.7 Systems out of service. The Fire Official shall be notified before disconnection and interruption of any fire protection, tests, repairs, alterations or additions are started and upon completion, and shall be advised of the extent of and reason for such work. Fire protection service shall be restored promptly.
Where a required fire alarm system is out of service for more than eight (8) hours in a twenty-four (24) hour period, or a required automatic sprinkler system is out of service for more than ten (10) hours in a twenty-four (24) hour period, the owner, occupant, or authorized representative shall notify the authority having jurisdiction and the building shall be evacuated unless the authority having jurisdiction allows an approved firewatch for all parties left unprotected by the shutdown until the system(s) has (have) been returned to service. When in the opinion of the Fire Official a required standpipe is out of service for more than ten (10) hours in a twenty-four (24) hour period, the owner, occupant, or authorized representative shall notify the authority having jurisdiction and the building shall be evacuated unless the authority having jurisdiction allows an approved firewatch for all parties left unprotected by the shutdown until the system has been returned to service.
901.7.4 Preplanned impairment programs.
9. Shall be in accordance with the Louisiana State Fire Marshal approval.
SECTION 906 — PORTABLE FIRE EXTINGUISHERS
906.2.2 Inspection tags. Portable fire extinguishers shall have current date tags issued and affixed by an individual or company license by the Louisiana State Fire Marshal.
SECTION 907 — FIRE ALARM AND
DETECTION SYSTEMS
907.9.1 One- and two-family dwellings. Every existing dwelling including one- and two-family dwellings shall be protected by an approved listed smoke alarm including, at a minimum, an operable single station ten-year, sealed lithium battery smoke alarm. In dwellings and dwelling units, a smoke alarm shall be mounted in accordance with NFPA 72 and International Residential Code standards. Single station smoke alarms shall be 10-year lithium battery-powered. Single station smoke alarms may be combination smoke and carbon monoxide detector. Multiple station smoke alarms may be connected to an approved household fire warning system and shall be listed to meet the installation requirements of NFPA 72 and the International Residential Code.
SECTION 912 — FIRE DEPARTMENT
CONNECTIONS
912.3.1 NOFD fire hose threads. New Orleans Fire Department fire hose connections shall meet the New Orleans Sewerage and Water Board specifications:
Large hose (2½ inches) — 7½ threads per inch (National Standard Thread)
Small hose (1½ inches) — 11½ threads per inch (Iron Pipe Thread)
CHAPTER 10
MEANS OF EGRESS
SECTION 1029 — ASSEMBLY
1029.9.9 Plan submittal of exit ways and aisles. A scale-drawn plan indicating the seating arrangements, location and width of exit ways and aisles, and the arrangement of furnishings or equipment, must be submitted by the building owner, manager, or authorized agent to the Fire Official for approval. The approved plan shall constitute the only acceptable arrangement until revised or additional plans are submitted and approved.
1029.9.10 Exposition plan. Plans for expositions, exhibits, trade shows, and similar events shall be submitted in an acceptable format to the Fire Official for approval prior to the move-in of any events.
CHAPTER 24
FLAMMABLE FINISHES
SECTION 2403 — PROTECTION OF
OPERATIONS
2403.2.7 Welding warning signs. Welding, cutting, and similar spark-producing operations shall not be conducted in or adjacent to flammable vapor areas or dipping or coating operations unless precautions have been taken to provide safety. Conspicuous signs with the following warning shall be posted in the vicinity of flammable vapor areas, dipping operations and paint storage rooms:
NO WELDING
THE USE OF WELDING OR CUTTING EQUIPMENT IN OR NEAR THIS AREA IS DANGEROUS BECAUSE OF FIRE AND EXPLOSION HAZARDS. WELDING AND CUTTING SHALL BE DONE ONLY UNDER THE SUPERVISION OF THE PERSON IN CHARGE. NO WELDING SHALL BE CONDUCTED WITHIN TWENTY (20) FEET OF ANY SPRAY BOOTH.
CHAPTER 31
TENTS AND OTHER
MEMBRANE STRUCTURES
SECTION 3103 — TEMPORARY TENTS
AND MEMBRANE STRUCTURES
3103.2 Approval required. Air-supported temporary membrane structures, tents, tarps, or canopies having an area in excess of 150 square feet (13.9 m2) shall not be erected, operated or maintained for any purpose without first obtaining a permit and approval from the fire code official.
Exceptions:
1. Tents used exclusively for recreational camping purposes.
2. Funeral tents and curtains or extensions attached thereto, when used for funeral services.
3103.6 Construction documents. A detailed site and floor plan for tents, canopies, or membrane structures with tables, chairs, or other movables shall be provided with each application for approval. The tent, canopy, or membrane structure floor plan shall indicate details of the means of egress facilities, seating capacity, arrangement of the seating and location and type of heating and electrical equipment.
SECTION 3104 — TEMPORARY AND PERMANENT TENTS AND MEMBRANE STRUCTURES
3104.15.5.1 Firewatch required. Any cooking operation within an air-supported temporary membrane structure, tent, tarp, or canopy that produces smoke or grease laden vapors and is not protected by an exhaust hood with an approved fire suppression system shall necessitate the employment of one or more approved firewatch personnel.
CHAPTER 56
EXPLOSIVES AND FIREWORKS
SECTION 5601 — GENERAL
5601.1.6 Transportation of explosives. Transportation of explosives in the following amounts shall require a New Orleans Police Department escort consisting of at least two motorcycle police officers:
USDOT 1.1, 1.2 or Class A: | Greater than 15 pounds N.E.C. (6.8 kg)
USDOT 1.2, 1.3, 1.4 or Class B: | Greater than 300 pounds N.E.C. (136 kg)
USDOT 1.4G or 1.5D or Class C: | Greater than 600 pounds N.E.C. (272 kg)
5601.2.4 Financial responsibility. Before a permit is issued pursuant to Section 5601.2, the applicant shall file with the jurisdiction a corporate surety bond in the principal sum of $1,000,000.00 or a public liability insurance policy for the same amount, for the purpose of the payment of all damages to persons or property which arise from, or are caused by, the conduct of any act authorized by the permit upon which any judicial judgment results. The fire code official is authorized to specify a greater or lesser amount when, in his or her opinion, conditions at the location of use indicate a greater or lesser amount is required. Government entities shall be exempt from this bond requirement.
SECTION 5608 — FIREWORKS DISPLAY
5608.2 Permit application. A permit must be obtained from the Fire Official to manufacture (compound), store, or use any fireworks or pyrotechnic special effects material in connection with motion picture, television, theatrical or group entertainment production. A permit for use shall be granted only to a competent operator approved by the Fire Official and who has an appropriate license from the New Orleans Fire Prevention Division.
5608.2.3 Standby personnel and equipment. The Fire Official may require the employment of one or more experienced New Orleans Fire Department firewatch personnel during the discharge of any permitted outdoor, indoor, or special effects pyrotechnic display. Said NOFD firewatch personnel shall be in uniform and subject to the Fire Official's orders at all times when so employed. Use of NOFD equipment may be required at the expense of the applicant.
5608.2.4 Commercial displays: license required. No person may engage in the business of producing commercial displays of fireworks without possessing a license issued by the New Orleans Fire Prevention Division. Conducting commercial displays of fireworks includes the display or discharge of Class 'B' or 'C' fireworks or 'D effects as entertainment before the public or a private group which has been admitted or permitted to view the display. See schedule of fees for Class 'B,' 'C,' or 'D' pyrotechnic or flame effects licenses. All pyrotechnic licenses are valid for one year following the date of issuance.
5608.2.5 Commercial displays: application for license. A person applying for a license to produce commercial displays of fireworks must:
1. Be a U.S. citizen.
2. Be at least 21 years of age.
3. Submit an application on the form provided by the New Orleans Fire Prevention Division.
4. Applicant must furnish the following:
a. A copy of his user permit from the Louisiana Department of Public Safety and Corrections and/or the Office of the State Fire Marshal as provided in R.S. 40:1472.3 and R.S. 51:650 et seq.
b. A copy of his distributor and/or importer permit(s) from the State Fire Marshal's Office as provided in R.S. 51:656.
c. A copy of his ATF documentation of clearance and permit(s) and/or license(s).
5608.2.6 Examination criteria. Applicant must successfully pass a written examination with a minimum score of 70 percent covering one or more of the following categories:
1. For an applicant seeking a Class 'B' license, the examination will cover the design, construction, storage, and use of fireworks as per NFPA 1123: Code for Fireworks Display and the New Orleans Fire Prevention Code including precautions and procedures for the safety and protection of spectators.
2. For an applicant seeking a Class 'C' license, the examination will cover the design, construction, storage and use of fireworks and systems used to produce flame effects as per NFPA 1126: Standard for the Use of Pyrotechnics Before a Proximate Audience, NFPA 160: Standard for the Use of Flame Effects Before an Audience, and the New Orleans Fire Prevention Code including precautions and procedures for the safety and protection of spectators.
3. For an applicant seeking a Class 'D' license, the examination will cover the design, construction/fabrication, installation, testing, control, operation, maintenance, equipment, procedures, and systems used to produce flame effects as per NFPA 160: Standard for the Use of Flame Effects Before an Audience, and the New Orleans Fire Prevention Code including precautions and procedures for the safety and protection of spectators.
4. For an applicant seeking a Class 'B' and 'C' license, the exams will cover those topics outlined in Subsections 1 and 2.
5. The tests noted above shall be developed and administered by members of the New Orleans Fire Prevention Division or a duly appointed agent/designee.
6. If a minimum score of 70 percent is not attained, the applicant must wait at least 30 days before retesting. The fees listed in Section 113.2 shall be applicable to all retests. A licensee whose license has been expired for 2 years or more and makes application for renewal must retake and pass the written test(s).
5608.2.7 Suspension, revocation, or refusal to renew a license or certificate. The Chief of Fire Prevention may suspend, revoke, or refuse to renew a license for a pyrotechnics technician/operator of commercial displays of fireworks if the licensee or registrant has caused or allowed a life safety hazard at a location at which the technician/operator:
1. Stores, handles, or prepares fireworks, special effect or pyrotechnic devices; or
2. Produces or conducts a commercial display of fireworks or special effects.
5608.2.7.1 Report. If an incident resulting in a life safety hazard is caused or allowed by a licensed technician/operator or registrant, he shall submit to the Chief of Fire Prevention upon request a report explaining the incident. Failure to submit the report shall constitute a violation for which a citation may be issued and, if after proper notice has been given and a hearing before a duly authorized administrative hearing officer has been conducted, may result in the revocation of the license or certificate.
5608.2.7.2 Disposal of product. A person whose license or certificate has been revoked must dispose of the fireworks, special effect or pyrotechnic devices in his possession within 30 days after receiving written notice to do so by the Chief of Fire Prevention. In complying with this subsection, the licensee or registrant may transfer the fireworks, special effects or pyrotechnic devices only to a person who is licensed to produce commercial displays of fireworks or who is otherwise permitted to lawfully purchase and possess fireworks or pyrotechnic devices.
CHAPTER 57
FLAMMABLE AND COMBUSTIBLE LIQUIDS
SECTION 5704 — STORAGE
5704.2.9.6.1 Locations where above-ground tanks are prohibited. Storage of flammable or combustible liquids in above-ground tanks outside of buildings is prohibited within the Inner Fire Limits as per the New Orleans Building Code.
Exception: All above-ground tanks that were legally installed prior to adoption of this code.
Plans and specifications for the installation or removal of every above-ground or underground combustible or flammable liquid storage tank shall be submitted to the Fire Official for approval.
5704.2.11.4.2 Leak detection. Underground storage tank systems shall be provided with an approved method of leak protection from any component of the system that is designed and installed in accordance with NFPA 30. Underground flammable or combustible liquid tanks of 1,000 gallons (3.79 cubic meters) capacity or larger shall be equipped at the time of installation with a vertical 6 inch (152 mm) diameter or larger perforated pipe installed within the sand or gravel backfill of the tank excavation hole to the depth of the lowest point of any tank or its foundation. A removable cover for inspection shall be provided over the perforated pipe. The cover shall be designed to withstand traffic over the tank area. A single pipe may serve more than one tank provided it will monitor leakage from the other tanks.
CHAPTER 80
REFERENCED STANDARDS
NFPA
NFPA-1 (2015) Uniform Fire Code
NFPA-101 (2015) Life Safety Code
NFPA-160 (2011) Standard for the Use of Flame Effects Before an Audience
NFPA-909 (2005) Code for the Protection of Cultural Resource Properties, Museums, Libraries, and Places of Worship
NFPA-914 (2010) Code for Fire Protection of Historic Structures
NFPA-1123 (2014) Code for Fireworks Display
NFPA-1124 (2006) Code for Manufacture, Transportation, Storage, and Retail Sales of Fireworks and Pyrotechnic Articles
NFPA-1126 (2011) Standard for the Use of Pyrotechnics Before a Proximate Audience
(M.C.S., Ord. No. 28108, § 1, 6-6-19; M.C.S., Ord. No. 30235, § 1, 2-27-25)