§ 17.12.940 — Amendment of Section 5003.9.8 of the 2025 California Fire Code
San José Municipal Code (Supp. No. 5: codified through Ordinance No. 31341, enacted August 25, 2026) · San José Municipal Code § 17.12.940
Corpus is an independent public-information project, not the official City of San Jose website. Stable reference: corpuslaw.us/code/52e342a7-4335-44ec-8a40-0540a2c5d0bc
17.12.940 - Amendment of Section 5003.9.8 of the 2025 California Fire Code.
Section 5003.9.8 of the 2025 California Fire Code is amended to read as follows: 5003.9.8 Separation of Incompatible Materials. Incompatible materials in storage and storage of materials that are incompatible with materials in use shall be separated where the stored materials are in containers having a capacity of more than 5 pounds (2 kg) or 0.5 gallons (2 L) or any amount of compressed gas. Separation shall be accomplished by at least one of the following: 1. Segregating incompatible materials in storage by a distance of not less than 20 feet (6096 mm) and in an independent containment system. 2. Isolating incompatible materials in storage by a noncombustible partition extending not less than 18 inches (457 mm) above and to the sides of the stored material in an independent containment system. 3. Storing liquid and solid materials in hazardous materials storage cabinets. 4. Storing compressed gases in cabinets or exhausted enclosures in accordance with Sections 5003.8.5 and 5003.8.6. Materials that are incompatible shall not be stored within the same cabinet or exhausted enclosure.
(Ord. 31258.)
Ask a question about San Jose law
Corpus searches the San Jose sections it holds and shows the ones that match, with their citations. Free, no sign-in.