Memphis Code of Ordinances § 13-26-1 Waste disposal—Construction plans approval and permit required.
Sec. 13-26-1. - Waste disposal—Construction plans approval and permit required.
A. Grease trap required. All food service establishments discharging wastewater to the city's wastewater facilities shall install, operate, and maintain a sufficiently sized oil and grease, water and solids separator (hereinafter called grease trap) necessary to prevent the accumulation of oil and grease in the sewer collection system. Approval of the City of Memphis, division of public works, shall be required during the construction plans approval process.
B. Design criteria. All grease traps used in conjunction with food service establishments shall have the capacity of 15 gallons per seat of dining capacity, except that no single grease trap shall be smaller than 750 gallons or larger than 3,000 gallons. In certain cases, multiple grease traps may be utilized. Alternative treatment technologies shall be considered on a case-by-case basis for food establishments that are to be located in an existing building where a large grease trap is not feasible.
C. General permit to discharge. All food establishments shall obtain a permit to discharge to the wastewater system from the approving authority. This permit shall be posted on the premises and renewed as needed.
(Ord. No. 5099, § 5(part), 2005)