2510.03 - Stairway markings.
In addition to the stairway marking requirements of the Ohio Fire Code and Ohio Building Code the following requirements shall apply whenever an interior exit enclosure connects more than three stories. 2510.03.1 Designation letters. Assignment of stairway designation letters shall start with stairway closest or next to the main entrance with the letter "A" and continue in a clockwise or left to right pattern. Numbering or naming of stairway is prohibited. 2510.03.2 No Reentry. Where stairway doors are locked from the stairway side to prohibit reentry to a floor, NO REENTRY shall be placed under the lower and upper terminus designation in 1- inch high block lettering. Additionally, the nearest floor above and below where a person can enter the floor from the stairway or where a telephone or two-way communication system is located shall be placed at the bottom of the sign in 1-inch high block lettering 2510.03.3 Schematic. A simplified schematic of the building footprint showing the building's exterior and general layout of the first floor or lobby level floor shall be displayed in the main entrance lobby and/or fire command center. 2510.03.4 Illustration. All stairway designation letters shall be clearly illustrated on the schematic and shall correlate with each stairway. A "YOU ARE HERE" designation should be indicated on the schematic showing its location in main entrance lobby and/or fire command center. 2510.03.5 Stairway information. Stairway information shall be included in the stairway location schematic indicating the following 1. Stairway Terminus (i.e., lowest and highest levels of the stairway) (Example: P-2 thru 14) 2. Availability of Roof Access (Example: Access to Roof or No Access to Roof) 3. Presence of a Standpipe (Example: Standpipe or No Standpipe)
(Ord. No. 1652-2022, § 1, 10-17-2022)
Ask a question about Columbus law
Corpus searches the Columbus sections it holds and shows the ones that match, with their citations. Free, no sign-in.