§ 18-28-908.3 — Location
Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-28-908.3
Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/5fb1bccc-f42e-43b7-b699-604c1d409d81
18-28-908.3 Location.
Cooling towers, evaporative condensers and fluid coolers shall be located to prevent the discharge vapor plumes from entering occupied spaces. Plume discharges shall be not less than 5 feet (1524 mm) above or 20 feet (6096 mm) away from any ventilation inlet to a building. Location on the property shall be as required for buildings in accordance with the Chicago Building Code. (Amend Coun. J. 9-14-21, p. 35949, Art. IX, § 5)
Ask a question about Chicago law
Corpus searches the Chicago sections it holds and shows the ones that match, with their citations. Free, no sign-in.
