§ 18.48.590 — CFC Chapter 9, Section 912.1—Installation

Long Beach Municipal Code (Supp. No. 53, Update 1: codified through Ordinance No. ORD-26-0027, enacted October 13, 2026) · Long Beach Municipal Code § 18.48.590

Corpus is an independent public-information project, not the official City of Long Beach website. Stable reference: corpuslaw.us/code/62b1e996-d809-4a62-b106-fa913f9114f8

18.48.590 - CFC Chapter 9, Section 912.1—Installation.

Section 912.1 of Chapter 9 of the California Fire Code is amended by the addition of Section 912.1.1 to read as follows: 912.1.1 Design. Fire department connections, where required, shall be provided with a minimum number of two (2) 2-½ inch inlets, regardless of the size of the fire sprinkler system. Where fire protection system demands are in excess of 1,000 gpm a minimum of four (4) 2-½ inch inlets shall be provided. Hazardous locations, high-rise buildings or where fire protection system demands are in excess of 2,000 gpm, a second fire department connection utilizing four (4) 2-½ inch inlets may be required at the discretion of the Fire Code Official.

(ORD-25-0019 § 1(Exh. A), 2025; ORD-22-0033 § 1(Exh. A), 2022)