Sec. 40-251. - District classifications.
(a) Storage of delivery tanks. It shall be unlawful to keep, house or store any delivery tank or any truck or other vehicle equipped with delivery tanks for flammable or combustible liquids, nor shall such liquids be stored in tanks outside above ground, except in oil districts as set forth in this section.
(b) [Storage of Class I liquids in vessels defined as tanks.] There shall be no storage of Class I liquids in vessels defined as tanks (60 gallons or more), or Class II liquids in amounts of 600 gallons or more unless a flammable or combustible liquid fire district is established, which requires filing an application with the chief of the fire prevention bureau (fire marshal) and receiving approval from the fire chief, the chief of the fire prevention bureau, the planning department, and the city council.
(c) Class A oil districts for storage above ground. Flammable liquids, which shall include highly flammable liquids comprising crude petroleum, refined oils, and all other liquids having a flash point of less than 100 degrees Fahrenheit (37.7 degrees Celsius), may be stored in tanks above ground only in districts as prescribed in this section and as amended by previous ordinance, and in such districts as may hereafter be created by ordinance.
(d) Class B oil districts for storage above ground. Combustible liquids, including such fuel oils and other liquids having a flash point between 100 degrees Fahrenheit (37.7 degrees Celsius) and 350 degrees Fahrenheit (176.6 degrees Celsius) may be stored in storage tanks outside above ground only in districts as prescribed by this section, and in such districts as may hereafter be created by ordinance or have been created by previous ordinance. Exceptions include tanks connected to any one oil burning or using appliance such as furnaces, water heaters, boilers, ranges and generators. The capacity of these tanks shall not be more than one 660-gallon tank or two tanks of aggregate capacity of 1,320 gallons or less installed in accordance with appropriate standards in lowest floor or basement.
(e) Classes of flammable and combustible liquids district.
Class (A) | Flash Point (degrees F) | Boiling Point (degrees F)
1 (A) | Below 100 | —
1A (A) | Below 73 | Below 100
1B (A) | Below 73 | At or above 100
1C (A) | 73—99 | —
Class (B)
2 (B) | 100—139 | —
3 (B) | 140 or above | Below 100
3A (B) | 140—199 | At or above 100
3B (B) | 200—350 | —
(f) Additional regulations. Nothing contained in this Code or in the ordinance adopting this code shall repeal or otherwise affect the validity of any previous district that has been created by ordinance.
(Ord. No. 36424, § 1, 10-21-03)