§ 49-1403 — Distance of vent pipe to trap
Omaha Municipal Code (Supp. No. 100, Update 2: codified through Ordinance No. 44760, enacted August 4, 2026) · Omaha Municipal Code § 49-1403
Corpus is an independent public-information project, not the official City of Omaha website. Stable reference: corpuslaw.us/code/63bd6c65-354b-4ee8-a851-fdf3aae4753f
Sec. 49-1403. - Distance of vent pipe to trap.
The vent pipe opening from a soil or waste pipe shall not be located below the weir of the trap. Exception: water closets or similar fixtures. No trap shall be placed more than the maximum horizontal developed length from the center of the vertical vent pipe to the weir of the trap shown in Table 49-1403 (see Figure 49-1403): Table 49-1403 Size of Fixture Drain (inches) | Maximum Distance Trap to Vent Maximum Slope 1¼ inch per foot | Sanitary Tee | A figure 5 type fitting Feet | Inches | Feet | Inches 1¼ | 5 | 0 | 2 | 6 1½ | 5 | 0 | 3 | 6 2 | 5 | 0 | 5 | 0 3 | 6 | 0 | 6 | 0 4 inch and larger | 10 | 0 | 10 | 0 Note: This distance shall not apply to water closets or similar fixtures.
(Ord. No. 40524, § 1, 10-20-15)
Ask a question about Omaha law
Corpus searches the Omaha sections it holds and shows the ones that match, with their citations. Free, no sign-in.
