13.12.050 - Electric and telephone.
A. All underground electrical conduits for residential service and telephone conduits, including communication facilities, shall be laid at such depth that the top of such conduits shall not be less than 45 inches and 30 inches, respectively, below the established grade of the parkway; provided, however, that in cases where the grades may not have been established, these depths shall be below the existing surface of the parkway. Major underground electrical conduits may be laid in the street and shall be not less than 30 inches below the existing surface or established grade of the street.
B. The underground electrical conduits for residential service and telephone conduits, including communication facilities, shall generally be laid a maximum of one foot from the edge of sidewalk and major electrical conduits in the street shall be laid at a location to be determined by the Public Utilities General Manager.
(Ord. 7362 § 5, 2017; Ord. 3927 § 2 (part), 1972)