Sec. 22-43. - Requirements for operating a central alarm station.
(a) Class I central station. Every class I central alarm station shall:
(1) Maintain an approved direct phone, and shall arrange for and pay all costs of equipment, installation, line lease, repair and removal;
(2) Maintain an approved coded register, and shall arrange for and pay all costs of, equipment, installation, line lease, repair and removal; and
(3) Report alarms. Any alarm or combination signal which indicates the presence of fire, smoke or water flow at the premises of a subscriber shall be deemed by a central alarm station to be an alarm of fire and the information shall be immediately transmitted to headquarters in the following sequence:
a. Voice communication over the direct phone giving the following:
1. The headquarters box number;
2. The name of the institution, building or premises involved;
3. The correct address of the premises involved, in numerical form, if possible;
4. The type of alarm, if known, including, but not limited to, waterflow, heat detector or manual station;
5. The location of the alarm installation on the premises, if known;
b. Tapping out three (3) rounds of the headquarters box number assigned to the protected premises involved on the coded register.
c. The department may permit forms of communication of fire alarm intelligence to headquarters, other than the voice communication and tapping prescribed in subsection (a) of this section.
(4) Whenever a required fire alarm system which is located on the premises of a subscriber is not in operation for any reason, the central alarm station shall dispatch a runner to such premises who shall remain thereon until such equipment is restored to operative condition.
(5) Submit to headquarters semiannually, on July first and on December thirty-first, a complete listing of its subscribers containing such information as may be requested by the department, for verification of records used for the transmission of alarms. Any changes in the subscriber list shall be brought to the department's attention within twenty-four (24) hours and confirmed in writing by the earliest first class mail.
(6) Maintain, at all times, at the central alarm station two (2) licensed operators, one of whom may be an apprentice and who shall have no other duties than that of operating the central alarm station.
(7) Maintain the central alarm station in conformance with the following National Fire Protective Association pamphlets:
a. Central Station Signaling Systems, Pamphlet No. 71, 1977;
b. Signaling Systems, Pamphlet No. 72-B, 1979;
c. Remote Station Protective Signaling Systems, Pamphlet No. 72-C, 1975; and
d. Proprietary Protective Signaling Systems, Pamphlet No. 72-D, 1979.
(b) Class II central alarm stations. Each class II central alarm station shall be equipped and staffed adequately to handle the number of subscribers which it services. The minimum requirements shall be:
(1) The maintenance of an approved direct phone to the department.
(2) Maintenance of one person on duty at all times whose only duty is to monitor the central alarm station equipment;
(3) Maintain on duty the number of operators, whose only duty is to monitor the central alarm station equipment, established by the department based on the number of alarms expected and the number of subscribers to the central alarm stations service;
(4) Report of subscribers required. Submission to headquarters semiannually, on July first and on December thirty-first a complete listing of its subscribers, containing such information as may be requested by the department for verification of records used for the transmission of alarms. Any changes in the subscriber list shall be brought to the department's attention within twenty-four (24) hours and confirmed in writing by the earliest first class mail.
(5) All equipment which is used and monitored by the central alarm station shall be approved, and the installation of the equipment shall be approved prior to it being put into operation.
(Ord. No. 650, § 1(238.7), 12-1-80)