§ 18.41.250 — Amend CRC Section R606.12.2.2.3—Reinforcement requirements for masonry elements
Long Beach Municipal Code (Supp. No. 53, Update 1: codified through Ordinance No. ORD-26-0027, enacted October 13, 2026) · Long Beach Municipal Code § 18.41.250
Corpus is an independent public-information project, not the official City of Long Beach website. Stable reference: corpuslaw.us/code/68ca0a59-8f0f-4644-847d-fb29bc2cf8ea
18.41.250 - Amend CRC Section R606.12.2.2.3—Reinforcement requirements for masonry elements.
Section R606.12.2.2.3 of the California Residential Code is amended to read as follows: R606.12.2.2.3 Reinforcement requirements for masonry elements. Masonry elements listed in Section R606.12.2.2.2 shall be reinforced in either the horizontal or vertical direction as shown in Figure R606.11(2) and in accordance with the following: 1. Horizontal reinforcement. Horizontal joint reinforcement shall consist of not less than one No. 4 bar spaced not more than 48 inches (1,219 mm). Horizontal reinforcement shall be provided within 16 inches (406 mm) of the top and bottom of these masonry elements. 2. Vertical reinforcement. Vertical reinforcement shall consist of not less than one No. 4 bar spaced not more than 48 inches (1,219 mm). Vertical reinforcement shall be within 8 inches (203 mm) of the ends of masonry walls.
(ORD-25-0019 § 1(Exh. A), 2025; ORD-22-0033 § 1(Exh. A), 2022; ORD-19-0031 § 1(Exh. A), 2019)