§ 17F.050.110 — Barricade Lighting
Spokane Municipal Code; partial · SMC 17F.050.110 · Effective
Corpus is an independent public-information project, not the official City of Spokane website. Stable reference: corpuslaw.us/code/68e4e5c3-f913-4bf0-a77d-b39fb87b19b4
Section 17F.050.110 Barricade Lighting
A person installing lighting in a public passageway which is part of a construction barricade must: A. install the wiring in metal raceways but may use flexible connections where sections of the barricade are to be removed; B. use lamps of at least one hundred watts; C. space lamps not more than thirty feet apart; D. install metal or glass guards over lamps; E. use red lamps at the extremities of the barricade and at sixty-feet intervals along the vehicular traffic side.
Date Passed: Monday, February 28, 2005 Effective Date: Saturday, April 2, 2005 ORD C33594 Section 4