Sec. 49-1145. - Type IV steam and hot water interceptors.

When connected to a sewer, all drains from high pressure blow-off or pump exhausts shall be installed as follows: (a) Connected to an interceptor of suitable size. (b) Made of cast-iron, concrete or steel construction. (c) Shall have at least a six-inch deep trap seal. (d) Shall have at least four-inch inlet and outlet waste connections. (e) Shall have a four-inch, independent vent installed through the roof. (f) Shall have stainless steel baffles and wear plates. (g) Shall have an inspection port. (h) Maintain a maximum discharge temperature of 140 degrees Fahrenheit. The vessel shall be equipped with a tempering assembly with drain fitting, self-contained temperature valve, temperature sensing bulb, bi-metal thermostat and strainer. (See Figure 49-1145.)

(Ord. No. 40524, § 1, 10-20-15)