§ 14.04.345 — Section R309.3.5 of the 2025 Edition of the California Residential Code is amended to read as follows and subsections are to be adopted as published by the State
Pasadena Municipal Code, California (Supp. No. 79: codified through Ordinance No. 7469, enacted May 18, 2026) · Pasadena Municipal Code § 14.04.345
Corpus is an independent public-information project, not the official City of Pasadena website. Stable reference: corpuslaw.us/code/6ce51b36-5879-4af0-adb2-f3a092724323
14.04.345 - Section R309.3.5 of the 2025 Edition of the California Residential Code is amended to read as follows and subsections are to be adopted as published by the State.
R309.3.5 Water supply. The water supply shall provide not less than the required design flow rate for sprinklers in accordance with Section R309.3.4.2 at a pressure not less than that used to comply with Section R309.3.6. Where a water supply serves both domestic and fire sprinkler systems, 5 gpm (19 L/min) shall be added to the sprinkler system demand at the point where the systems are connected, to determine the size of common piping and the size of the total water supply requirements where no provision is made to prevent flow into the domestic water system upon operation of a sprinkler. For multipurpose piping systems, the 5 gpm (19 L/min) demand shall be added at the domestic connection nearest the design area. This demand may be split between two domestic connections at 2.5 gpm (10 L/min) each. Hydraulic calculations shall include a 10% safety margin.
(Ord. No. 7461, § 5, 11-10-2025)
Ask a question about Pasadena law