§ 18.48.560 — CFC Chapter 9, Section 907—Fire alarm and detection systems

Long Beach Municipal Code (Supp. No. 53, Update 1: codified through Ordinance No. ORD-26-0027, enacted October 13, 2026) · Long Beach Municipal Code § 18.48.560

Corpus is an independent public-information project, not the official City of Long Beach website. Stable reference: corpuslaw.us/code/6cf4893a-c78e-4e1f-9783-8a904e67a5ae

18.48.560 - CFC Chapter 9, Section 907—Fire alarm and detection systems.

Section 907 of Chapter 9 of the California Fire Code is amended by the addition of Sections 907.11 and 907.12 to read as follows: 907.11 Fire alarm upgrade. All existing multi-family residential, hotels, motels and high-rise buildings shall upgrade the existing fire alarm system to current code, at the time of replacement of the existing non-functioning fire alarm control panel. 907.12 Firefighter smoke removal system. A natural or mechanical Fire Department approved ventilation system for the removal of products of combustion shall be provided above and below grade on every level, at the discretion of the Fire Code Official, and shall consist of one of the following: 1. Panels or windows in the exterior walls which can be opened remotely from an approved location other than the fire floor. Such venting facilities shall be provided at the rate of twenty square feet per lineal feet of exterior wall in each story and shall be distributed around the perimeter at not more than fifty-foot intervals. Such windows or panels and their controls shall be clearly identified. Exception: When a complete automatic fire extinguishing system is installed, windows or panels manually openable from within the fire floor or approved fixed tempered glass may be used in lieu of the remotely operated openable panels and windows. Such windows shall be clearly identified and shall be of the size and spacing called for above. 2. When a complete and approved automatic fire extinguishing system is installed, the mechanical air-handling equipment may be designed to accomplish smoke removal. Under fire conditions, the return and exhaust air shall be moved directly to the outside without recirculation to other sections of the building. The air-handling system shall provide a minimum of one exhaust air change each ten minutes for the area involved. The system shall utilize a firefighter smoke exhaust panel located at the main entrance to the building or as required by the Fire Code Official and shall be permanently labeled "Fire Department Smoke Evacuation Use Only". Operation of the system shall be by the use of a Knox key switch. 3. Any other design which will produce equivalent results as approved by the Fire Code Official.

(ORD-25-0019 § 1(Exh. A), 2025; ORD-22-0033 § 1(Exh. A), 2022)

Ask a question about Long Beach law

Corpus searches the Long Beach sections it holds and shows the ones that match, with their citations. Free, no sign-in.