Philadelphia Code Subcode R, § G2427 (503) VENTING OF APPLIANCES
SECTION G2427 (503) VENTING OF APPLIANCES
* * *
[Pursuant to the UCC, delete Section G2427.2.2 and replace as follows:]
R-G2427.2.2 (503.2.4) Appliances with integral vents. Appliances incorporating integral venting means shall be installed in accordance with Section G2427.8.
* * *
[Pursuant to the UCC, delete Section G2427.5.1 and replace as follows:]
R-G2427.5.1 (503.5.1) Factory-built chimneys. Factory-built chimneys shall be listed in accordance with UL 103 and installed in accordance with manufacturer’s instructions. Factory-built chimneys used to vent appliances that operate at a positive vent pressure shall be listed for such application.
* * *
[Pursuant to the UCC, delete Section G2427.5.4 and replace as follows:]
R-G2427.5.4 (503.5.5) Size of chimneys. The effective area of a chimney venting system serving listed appliances with draft hoods, Category I appliances, and other appliances listed for use with Type B vents shall be determined in accordance with one of the following methods:
1. The provisions of Section G2428.
2. The effective areas of the vent connector and chimney flue of a venting system serving a single appliance with a draft hood shall be not less than the area of the appliance flue collar or draft hood outlet, nor greater than seven times the draft hood outlet area.
3. The effective area of a chimney flue or a venting system serving two appliances with draft hoods, shall be not less than the area of the larger draft hood outlet plus 50 percent of the area of the smaller draft hood outlet. Nor greater than seven times the smallest draft hood outlet.
4. Chimney venting systems using mechanical draft shall be sized in accordance with approved engineering methods.
5. Other approved engineering methods.
* * *
[Pursuant to the UCC, delete Section G2427.5.10 and replace as follows:]
R-G2427.5.10 (503.5.11) Insulation shield. Where a factory-built chimney passes through insulated assemblies, an insulation shield constructed of steel having a thickness of not less than 0.0187 inch (0.475 mm) (nominal 26 gage) shall be installed to provide clearance between the chimney and the insulation material. The clearance shall be not less than the clearance to combustibles specified by the chimney manufacturer’s installation instructions. Where chimneys pass through attic space, the shield shall terminate not less than 2 inches (51 mm) above the installation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed chimney system shall be installed in accordance with the manufacturer’s installation instructions.
* * *