Occupancy requirements.
Kansas City Code § 18-231
in effectSec. 18-231. - Occupancy requirements.
(a) Generally.
(1) Group US occupancies shall be a subsurface structure formed out of a horizontal layer of solid limestone by the room-and-pillar method of mining when such underground space is developed into community housing, manufacturing, offices, warehousing, storage facilities and other classes of occupancy.
(2) Since the basic underground space is formed of solid limestone, it shall be considered type I construction as defined in the International Building Code. As such, the area of the underground space may be unlimited.
(3) Each individual subsurface building shall be classified and developed in accordance with the applicable requirements set forth in chapters 3, 4, and 5 of the International Building Code as adopted by article II of this chapter.
(b) Exit facilities; refuge space.
(1) The streets and roadways throughout the underground space shall be considered to be horizontal, continuous and unobstructed means of egress to either the exterior of the underground space through portals or to a refuge area in another building in the underground space.
(2) One or more refuge areas shall be provided in large underground spaces whenever the travel distance from any building exit to the exterior exit of the underground space exceeds 3,500 feet (1067 m). It shall provide ten square feet of floor area for each person it is intended to serve. This area may be used during normal operations as a lunchroom, public restrooms or security station or for maintenance, office or other uses provided it is continually available and usable as a refuge area during normal business hours.
(c) Light, ventilation and sanitation. All portions of group US occupancies customarily used by human beings shall be provided with artificial light, air and sanitary facilities as required in this article for the individual occupancy of the developed areas. Toilet facilities shall be located either in the developed occupancies or conveniently in the underground space.
(d) Shaft enclosures. Elevator shafts, vent shafts, exit stairways and other vertical openings extending to the exterior or other floors of the underground space shall be enclosed with two-hour fire resistive construction.
(e) Fire protection systems. Fire protection systems shall be provided as required by this article and the International Building Code.
(f) Special hazards.
(1) No hazardous materials, liquids or chemicals shall be stored in group US occupancies except as permitted in tables no. 307.1 (1), 307.1 (2), of the International Building Code.
(2) Every room containing a boiler, furnace or central heating plant shall be separated from the rest of the underground space by at least two-hour fire resistive construction, and shall have a minimum of two fire-rated means of access, one for personnel use not less than two feet (610 mm) in width and one large enough to permit removal of the largest unit, and no other openings shall be permitted from this room to the underground space other than pipes, ducts or conduits, properly sealed. All combustion air, chimney or flue vents, relief vents and fuel piping shall enter this boiler-furnace room directly to and from the exterior. All other installation, operating and maintenance provisions shall be as required by this chapter.
(g) Emergency and exit signs.
(1) All streets and roadways within the underground space shall be identified for emergency purposes by readily visible signs. Lettering shall be not less than four inches (102 mm) high and not less than one-half inch (12.7 mm) wide and shall be of luminescent finish. The signs shall not be higher than four feet (1219 mm) above the road surface.
(2) Each pillar on each side of a street or roadway shall be identified by name, letter or number, and below each street sign shall be a large directional arrow with the word "EXIT" in letters not less than six inches (152.4 mm) high and not less than three-fourths inch (19 mm) wide. All signs and letters shall be of reflective or luminescent paint. The exit arrow shall point in the direction of the nearest exit or horizontal exit.
(3) All street identification and exit routing shall be shown on maps of the Underground space, in color, shall be distributed to all personnel using the facility, shall be posted in all offices, shall be posted at the entrances and exits, and shall be given to the police and fire departments having jurisdiction in the facility. The maps shall be brought up to date annually as required to be current.
(h) Central control station; alarm devices.
(1) Every group US occupancy shall contain a central control station near an entrance portal of the underground space. Such station may serve as a guardroom, security office or manager's office. The station shall contain an annunciator panel which has a separate electrically operated visual signaling device for each remote alarm initiating (automatic) device, such as fire detectors, smoke detectors and water flow switches, and for each manual alarm initiating device, such as a manual pull station or manually operated switch.
(2) At or near the annunciator panel shall be a large map indicating in reasonable detail the entire underground space, identifying by letter, name and number each pillar, each building and each tenant space. The location of each manual or automatic detection device shall be identified by a pilot light with a coded letter or number to match the visual signal on the annunciator panel and wired in parallel so that the person in charge or firefighters can immediately locate an emergency.
(3) Any one of the remote manual or automatic alarm indicating devices shall set off a general alarm through audible signals such as bells, horns, sirens or a voice system capable of being operated from the central control station on a general as well as a selective basis dependent upon the compartmentation involved. The alarm should be designed to be heard by all occupants within the building or designated portions thereof as specified for the voice communication system, as well as transmitting an alarm automatically to the local fire department.
(Ord. No. 200418, § 1, 6-18-20)
Source: City of Kansas City, Missouri, Code of Ordinances, Charter and Zoning and Development Code (Municode Library, library.municode.com)URL: https://library.municode.com/mo/kansas_city/codes/code_of_ordinances?nodeId=PTIICOOR_CH18BURECO_ARTXIUNSP_S18-231OCREFetched: 10/28/2026