§ 57.324.10.1 — EXTINGUISHERS
Los Angeles Municipal Code (2026 Rev. 9, current through legislation effective June 30, 2026) · Los Angeles Municipal Code § 57.324.10.1
Corpus is an independent public-information project, not the official City of Los Angeles website. Stable reference: corpuslaw.us/code/74adcb63-f1a4-4d34-834c-f166fba1c6ba
SEC. 57.324.10.1. EXTINGUISHERS.
A minimum of one 4A/60B:C dry chemical extinguisher shall be maintained at each of the following locations: 1. At each electrical panel. 2. At each corner of the work area. Where no clear corners exist, four extinguishers shall be placed around the outermost wall of the work area so that they are evenly spread around the perimeter of the outermost wall. 3. Within 5 feet of the external entry to the shower room from the work area. 4. Within 5 feet of the external entry to the shower room from the clean room. 5. The maximum distance of travel to an extinguisher shall be no greater than 75 feet. EXCEPTION: Where the total abatement containment area is less than 1,000 square feet, one 4A/60B:C extinguisher shall be provided, and the maximum distance of travel to an extinguisher shall be no greater than 75 feet.