§ 9-22 — Amendments to the 2023 National Electrical Code

Code of the City of Glendale, Arizona (Supp. No. 115: codified through Ordinance No. O26-19, adopted April 14, 2026) · Glendale City Code § 9-22

Corpus is an independent public-information project, not the official City of Glendale website. Stable reference: corpuslaw.us/code/7571c93a-d117-4586-967e-df0d0398f215

Sec. 9-22. - Amendments to the 2023 National Electrical Code.

Article 90 - Introduction Section 90.1 (A) is amended to read as follows: 90.1 (a) Practical safeguarding. The purpose of this code is the practical safeguarding of persons and property from hazards arising from the use of electricity. Any and all electrical work for light, heat, power, or any other purposes shall be installed in conformity with the rules and regulations as set forth in this code and that document titled, National Electrical Code, 2023 edition, also known as NFPA 70, and in conformity with the rules, policies, regulations and amendments as set forth by the building official. This Code is not intended as a design specification or an instruction manual for untrained persons. Section 90.2(C)(7) is added to read as follows: Special Inspection. The City of Glendale requires Special Electrical Inspections for the types of work specified below as amended by adding sections 90.2(C)(7) and 90.2(C)(8) Special Electrical Inspections include, but are not limited to, testing or observation of the work assigned for conformance with the approved design drawings and specifications, and submission of appropriate inspection reports or certificates to the City of Glendale Electrical Inspector. The Special Electrical Inspector shall be a qualified person who demonstrates competence to the satisfaction of the Building Official for the type of work requiring Special Inspection. These individual(s) or firm(s) shall be responsible for performing the Special Inspection tasks and reports required by the City of Glendale. The Special Electrical Inspector(s) shall be an independent, third-party individual, firm or testing agency and shall not be the installing contractor or any other person responsible for the work. Electrical Special Inspection: 1. Ground-fault protection performance tests for equipment provided or required to have ground-fault protection. 2. Switchboard, panelboards, motor control center, and all other equipment rated 1,000 amps or more; or over 600 volts. (over-potential test, also known as a dielectric withstand test, and commonly referred to as a hi-pot test.) 3. Emergency and standby power systems including: switchboards, panelboards, distribution boards, transfer equipment, power source, conductors, fire pumps, exhaust and ventilation fans. 4. Other special inspections as required by the building official. Section 90.2(C)(8) is added to read as follows: Electrical observation. Electrical observation by the 'Registrant of Record' shall be provided for the following installations: 1. Installation or alteration of that portion of a health care facility electrical system which fall within the scope of article 517, Part 3- "Essential Electrical System" of the 2023 National Electrical Code. 2. Installations or alterations of high voltage electrical systems, which exceed 600 volts. 3. Installations or alterations of electrical systems within locations classified as hazardous by the provisions of the 2023 National Electrical Code, or the currently adopted International Fire Code, except for gasoline dispensing installations and systems located within storage garages, repair garages or lubritorium's. The owner shall employ the Engineer responsible for the electrical design, or another Engineer designated by the Engineer responsible for the electrical design to perform visual observation of complex electrical equipment and systems for general conformance to the approved plans and specifications, including but not limited to, placement and interconnection of equipment. Electrical observation shall be performed at intermediate significant stages of the construction progression and when installation is complete and ready to be inspected by the Building Official. Certificates of Electrical Observation shall be completed and sealed by the Engineer of Record for all life safety items as one of the requirements prior to release of a temporary certificate of occupancy. All certificates of Electrical Observation shall be completed and sealed prior to the project's final approval and the electrical portion of the certificate of occupancy is completed. Article 100 Definitions. Article 100 is amended by revising the definition of the following items to read as follows: Kitchens. Commercial and Institutional Kitchens and Bars. For the purposes of this section, a kitchen or bar is defined as any area where food or beverage is prepared, served or dispensed. Article 210 - Branch Circuits Section 210.8(B)(2) is amended to read as follows: (2) Kitchens: Commercial and Institutional Kitchens and bars. For the purposes of this section, a kitchen or bar is defined as any area where food or beverage is prepared, served or dispensed. Sections 210.52(C)(2) and 210.53(C)(3) are amended; delete the text and replace with the following: 210.52(C)(2) Island and peninsular countertops and work surfaces. At least one receptacle shall be installed at each island and peninsular countertop space with a long dimension of 600 mm (24 in.) or greater and a short dimension of 300 mm (12 in.) or greater. A peninsular countertop is measured from the connected perpendicular wall. 210.52(C)(3) Receptacle outlet location. Receptacle outlets shall be located in one or more of the following: 1. On or above, but not more than 20 inches (508 mm) above, the countertop or work surface. 2. In a countertop using receptacle outlet assemblies listed for the use in countertops. 3. In a work surface using receptacle outlet assemblies listed for use in work surfaces or listed for use in countertops. Receptacle outlets rendered not readily accessible by appliances fastened in place, appliance garages, sinks or range tops as covered in 210.52(C)(1), Exception No. 1, or appliances occupying assigned paces shall not be considered as these required outlets. Exception: To comply with the following conditions (1) and (2), receptacle outlets shall be permitted to be mounted not more than 12 inches (300 mm) below the countertop or work surface. Receptacles mounted below a countertop or work surface in accordance with this exception shall not be located where the countertop or work surface extends more than 6 inches (150 mm) beyond its support base. 1. Construction for the physically impaired. 2. On island and peninsular countertops or work surfaces where the surface is flat across its entire surface (no backsplashes, dividers, etc.) and there are no means to mount a receptacle within 20 inches (500 mm) above the countertop or work surface, such as an overhead cabinet. Informational Note No. 1: See 406.5(E) for installation of receptacles in countertops and 406.5(F) for installation of receptacles in work surfaces. See 380.10 for installation of multioutlet assemblies. Informational Note No. 2: See Informative Annex J and ANSI/ICC A117.1-2009, Standard on Accessible and Usable Buildings and Facilities, for additional information. Article 230 Services Section 230.2 is amended by adding the following sentence to the end of the first paragraph: No electrical service on one property shall supply power to another separate and distinct property unless these properties are legally combined and under the same ownership. Section 230.43 is amended to read as follows: Section 230.43. Wiring methods for 600 volts, nominal, or less. Service-entrance conductors shall be installed in accordance with the applicable requirements of this code covering the type of wiring method used and shall be limited to the following methods: 1. Rigid metal conduit 2. Intermediate metal conduit 3. Wire ways 4. Bus ways 5. Auxiliary gutters 6. Rigid non-metallic conduit may be used underground 7. Schedule 80 rigid non-metallic conduit may extend above ground to the service equipment. (Informational note): Refer to the serving utility company's requirements for additional information on installing service-entrance conductors on or within buildings and underground laterals serving the premises. Article 250 Grounding and Bonding Section 250.118, Types of equipment grounding conductors. Amend item #4 as follows: 4. Electrical metallic tubing with an additional equipment grounding conductor. Article 300 Wiring Methods Section 300.4(D) Exception 1 is amended to read as follows: Exception 1: Steel plates, sleeves, or the equivalent shall not be required to protect rigid metal conduit, intermediate metal conduit, or electrical metallic tubing. Rigid nonmetallic conduit (PVC conduit) is required to be protected. Section 310.12 is amended to read as follows: 310.12: 120/240-Volt, Single-Phase Dwelling Services and Feeders. For one-family dwellings and the individual dwelling units of two-family and multifamily dwellings, service and feeder conductors supplied by a single-phase, 120/240-volt system shall be permitted to be sized in accordance with 310.12(A) through (D). (A) Services. For a service rated 100 amperes through 400 amperes, the service conductors supplying the entire load associated with a one-family dwelling, or the service conductors supplying the entire load associated with an individual dwelling unit in a two-family or multifamily dwelling, shall be permitted to have an ampacity not less than 83 percent of the service rating. If no adjustment or correction factors are required, Table 310.12(A) shall be permitted to be applied. (B) Feeders. For a feeder rated 100 amperes through 400 amperes, the feeder conductors supplying the entire load associated with a one-family dwelling, or the feeder conductors supplying the entire load associated with an individual dwelling unit in a two-family or multifamily dwelling, shall be permitted to have an ampacity not less than 83 percent of the feeder rating. If no adjustment or correction factors are required, Table 310.12(A) shall be permitted to be applied. (C) Feeder Ampacities. In no case shall a feeder for an individual dwelling unit be required to have an ampacity greater than that specified in 310.12(A) or (B). (D) Grounded Conductors. Grounded conductors shall be permitted to be sized smaller than the ungrounded conductors, if the requirements of 220.61 and 230.42 for service conductors or the requirements of 215.2 and 220.61 for feeder conductors are met. Where correction or adjustment factors are required by 310.15(B) or (C), they shall be permitted to be applied to the ampacity associated with the temperature rating of the conductor. Informational Note No. 1: See 240.6(A) for standard ampere ratings for fuses and inverse time circuit breakers. Informational Note No. 2: See Informative Annex D, Example D7. Section 334.10 is amended to read as follows: 334.10 Uses Permitted. Type NM and Type NMC cables shall be permitted to be used in the following, except as prohibited in 334.12: 1. One- and two-family dwellings and their attached or detached garages, and their storage buildings. 2. Multi-family dwelling units and their detached garages — permitted to be of Types III, IV and V construction. 3. Cable trays in dwellings in accordance with 334.10(1) or in dwelling units, in accordance with 334.10(2) where the cables are identified for the use. Article 410 Luminaires, Lampholders, and Lamps Section 410.36(B) is amended by adding a second paragraph to read as follows: Intermediate or heavy-duty ceiling systems shall be used for the support of luminaires (lighting fixtures). All light fixtures shall be positively attached to the suspended ceiling system. The attachment device shall have a capacity of 100 percent of the lighting fixture weight acting in any direction. Luminaires (fixtures) weighing less than 56 pounds and track lighting shall have two 12 gauge wires attached at opposing corners of the luminaire(s) (fixture) or track lighting strip to the structure above. These wires may be slack, and shall contain, at a minimum, at least 3 tight twists within a 3-inch length of the wire at each end. Recessed luminaire housings, exit signage, all single bulb fixtures and emergency unit equipment that are installed within or on a suspended ceiling shall have a minimum of at least one 12-gauge wire attached to the structure above and this wire may be slack and shall contain, at a minimum, at least 3 tight twists of the wire within a 3-inch length at each end. Luminaires weighing more than 50 pounds shall comply with NEC 314.27 (a)(2).

(Ord. No. O25-51, § 1, 12-9-25)

Ask a question about Glendale law

Corpus searches the Glendale sections it holds and shows the ones that match, with their citations. Free, no sign-in.