§ 18.40.170 — Amend CBC Section 907.3.1 and Exception 2—Duct smoke detectors
Long Beach Municipal Code (Supp. No. 53, Update 1: codified through Ordinance No. ORD-26-0027, enacted October 13, 2026) · Long Beach Municipal Code § 18.40.170
Corpus is an independent public-information project, not the official City of Long Beach website. Stable reference: corpuslaw.us/code/75b498fd-5ed9-45bf-946d-ee57ec1238d9
18.40.170 - Amend CBC Section 907.3.1 and Exception 2—Duct smoke detectors.
Section 907.3.1 and Exception 2 of Section 907.3.1 of the California Building Code is amended to read as follows: 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm system or sprinkler monitoring system, when one is installed. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with this code and the California Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where above duct smoke detectors activate the building's alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm or sprinkler monitoring system, actuation of a duct smoke detector shall activate a visible and an audible signal in an approved location. Duct smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as an air duct detector trouble.
(ORD-25-0019 § 1(Exh. A), 2025)
Ask a question about Long Beach law
Corpus searches the Long Beach sections it holds and shows the ones that match, with their citations. Free, no sign-in.