Code of Ordinances of the City of Huntsville, Alabama (Supp. No. 30 (codified through Ord. No. 26-196, adopted March 12, 2026) with enacted ordinances through Ord. No. 26-837 (September 24, 2026) applied from official council minutes and ordinance copies) · Huntsville Code of Ordinances, App. B, art. 4, § 4.16

Corpus is an independent public-information project, not the official City of Huntsville website. Stable reference: corpuslaw.us/code/775a1dde-c11c-4e69-bd02-60ab48ce0bd4

4.16. - Design standards.

A. A minimum safety factor for stability of 1.5 must be documented with adequate data, including triaxial shear tests, multiple analyses (sliding wedge, infinite slope and slip circle analyses) and confident ground water (piezometer) measurements and control. B. A minimum safety factor of 3.0 shall be required for bearing capacity.