Installation.
Gilbert Town Code § 10-92
in effectSec. 10-92. - Installation.
(a) Requirements. A backflow prevention assembly approved by the department shall be installed on each water service line to a customer's water system, except for single-family residences exempt in the state administrative code, section R-18-4-115(C). As to any consumer using a water system without such assembly on or prior to the date that Ordinance No. 769 became effective, such backflow prevention assembly shall be installed within 180 days after such effective date. As to all other water service lines to a consumer's water system, such approved backflow prevention assembly shall be so installed prior to issuance of any certificate of occupancy for the structure to which the water system will provide service.
(b) Conditions requiring installation. An approved backflow prevention assembly shall be installed on each water service line to a consumer's water system where the following conditions exist:
(1) Premises having an auxiliary water system, unless such auxiliary water system is accepted as an additional source by the town and the source is approved by the agency and local authority.
(2) Premises where any substances exist which can create an actual or potential health hazard to the public water supply system.
(3) Premises having internal cross connections that, in the judgment of the officer, are not correctable, or intricate plumbing arrangements which make it impractical to determine whether or not cross connections exist.
(4) Premises where, because of security requirements or other prohibitions or restrictions, it is impossible or impractical to make a complete cross connections survey.
(5) Premises having a repeated history of cross connections being established or reestablished.
(c) Types of assemblies required. The following approved backflow prevention assemblies shall be installed on each water line to a consumer's water system serving types of facilities including but not limited to the following, unless the officer determines an alternate type of protection is either required or adequate to protect the public water supply or that no actual or potential hazard to the public water supply system exists:
(1) Aircraft and missile plants—RP.
(2) Automotive plants—RP.
(3) Auxiliary water systems (interconnected)—RP.
(4) Auxiliary water systems (not interconnected)—DC.
(5) Beverage bottling plants—DC.
(6) Breweries—RP.
(7) Buildings greater than three stories or greater than 34 feet in height from curb level—DC.
(8) Buildings with house pumps and/or potable water storage tank—DC.
(9) Canneries, packinghouses and reduction plants—RP.
(10) Car wash with water reclamation system—RP.
(11) Centralized heating and air conditioning plants—RP.
(12) Chemical plants—RP.
(13) Chemically treated potable or nonpotable water systems—RP.
(14) Commercial laundries—DC.
(15) Dairies and cold storage plants—DC.
(16) Dye works—RP.
(17) Film processing laboratories—RP.
(18) Food processing plants—DC.
(19) High schools and colleges—DC.
(20) Holding tank disposal stations—RP.
(21) Hospitals and mortuaries—RP.
(22) Medical and dental buildings, sanitariums, rest and convalescent homes—DC.
(23) Mobile home and travel trailer parks—RP.
(24) Irrigation systems (premises having separate systems, such as parks, playgrounds, cemeteries, golf courses, schools, estates, ranches, etc.)—RP.
(25) Laboratories using toxic materials—RP.
(26) Manufacturing, processing and fabricating plants using toxic materials—RP.
(27) Manufacturing, processing and fabricating plants using nontoxic materials—RP.
(28) Motion picture studios—RP.
(29) Oil and gas production facilities—RP.
(30) Paper and paper production plants—RP.
(31) Plating plants—RP.
(32) Radioactive materials processing facilities—RP.
(33) Restricted, classified or other closed facilities—RP.
(34) Rubber plants—RP.
(35) Sand and gravel plants—RP.
(36) Sewage and storm drainage facilities—RP.
(37) Any premises where a cross connection is maintained—RP.
(38) Water trucks, temporary water storage units, hydraulic sewer cleaning equipment, street sweepers, steel wheeled rollers—RP or AG.
(39) Any premises where water supplied by the town is subject to deterioration in sanitary quality and its entry into the public water system is permitted—DC.
(40) Any connection to a fire hydrant (except fire department equipment)—RP or AG.
(Ord. No. 869, § I(7-14-5), 6-7-94)
Source: Town of Gilbert, Arizona, Town Code (Municode Library, library.municode.com)URL: https://library.municode.com/az/gilbert/codes/code_of_ordinances?nodeId=CO_CH10BUCORE_ARTIIIBAPR_DIV2DEAS_S10-92INFetched: 11/1/2026