§ 907 — FIRE ALARM AND DETECTION SYSTEMS
The Philadelphia Code (2026 Code: The Philadelphia Code and Home Rule Charter current through October 8, 2026) · Philadelphia Code Subcode B, § 907
Corpus is an independent public-information project, not the official City of Philadelphia website. Stable reference: corpuslaw.us/code/7b6dd997-60ed-40bb-ade8-6a0d1981c25c
SECTION 907 FIRE ALARM AND DETECTION SYSTEMS
* * * [F] 907.2 Where required-new buildings and structures. * * * [F] 907.2.3 Group E. * * * [Add Section B-907.2.3.1 as follows:] [F] B-907.2.3.1 Occupant load of 50 or less. Where a manual fire alarm system is not provided in Group E occupancies with an occupant load of 50 or less, interconnected smoke alarms shall be installed in accordance with Section 907.2.10 and a minimum of one smoke alarm shall be installed in each classroom or child care room. * * * [F] 907.6 Installation and monitoring. * * * [F] 907.6.4 Zones. * * * [Delete Section 907.6.4.1 and replace as follows:] [F] B-907.6.4.1 Zoning indicator panel. A zoning indicator panel and the associated controls shall be provided at a visible location at the main entrance of the building or other location approved by the Fire Department. The visual zone indication shall lock in until the system is reset and shall not be cancelled by the operation of an audible-alarm silencing switch. * * * [Add Section B-919 as follows:]