Sec. 591-405. - Required water supply for fire protection.
(a) All Class 1 structures or portions of Class 1 structures hereafter constructed shall be provided with a water supply capable of providing the required fire flow, for fire-fighting purposes for a minimum period of two (2) hours. The water supply shall be from a source as set forth in Section 903.2 of 675 IAC 22. (b) In setting the requirements for fire flow, the fire prevention chief shall use 675 IAC 22, Table A-111-A-1 as a guide. Notwithstanding the provisions of this subsection, a reduction in required fire flow of seventy-five (75) percent is allowed when the building is provided with an approved automatic sprinkler system. The resulting fire flow shall not be less than one thousand (1,000) gpm at twenty (20) psi residual. (c) An owner or occupant who seeks a variance from an order issued under this Section 591-405 may file a variance with the Indiana Fire Prevention and Building Safety Commission as set forth in IC 36-8-17.
(G.O. 43, 2002, § 2)