For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 695.3 — Power Source(s) for Electric Motor-Driven Fire Pumps. {Introductory paragraph as in NEC}

Baltimore City Code (current through Ord. 26-129 (July 17, 2026); publication of Oct. 18, 2026) · Baltimore City Code, Building Codes, Part III, Section 695.3

Corpus is an independent public-information project, not the official City of Baltimore website. Stable reference: corpuslaw.us/code/816c1055-a54b-410c-9483-497b000f5a00

Section 695.3. Power Source(s) for Electric Motor-Driven Fire Pumps. {Introductory paragraph as in NEC}

(A) - (C) {As in NEC} (D) On-Site Standby Generator as Alternate Source. {Introductory paragraph as in NEC} (1) Capacity. {As in NEC} (2) Connection. A tap ahead of the generator disconnecting means is required. (3) Adjacent Disconnects. The requirements of § 430.113 of this Code apply. (E) - (I) {As in NEC}

Ask a question about Baltimore law

Corpus searches the Baltimore sections it holds and shows the ones that match, with their citations. Free, no sign-in.