Sec. 49-1520. - Pressure reducing valve.
Installations of pressure reducing valves shall be subject to the following provisions: (a) Installed in all buildings where the inlet pressure exceeds 80 psi. (b) Maximum setting when fully adjusted will not be more than 80 psi. (c) Pressure reducing valves with thermal bypass shall meet ANSI 1003 and shall be installed in the cold water line on the main side of the meter. (d) Exception: In commercial buildings, systems designed by a mechanical engineer licensed to practice in the State of Nebraska for special applications may exceed 80 psig, but in no case shall it exceed 125 pounds. In no case shall the high pressure line serve a water heater.
(Ord. No. 40524, § 1, 10-20-15)